1 Bed Room - Mental Health, 18m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code 1BR-MH-18-I
Net Room Area Briefed 18
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff; 1-2 visitors
Description / Special Requirements Single bed room for general mental health patients; natural light and outlook is essential; The room is to be internally lockable with a master keyed lock from the outside; All fittings are to have a breaking strain of not more than 15kg. All glazing (including external windows) is to comply with relevant Standards for Mental Health Facilities. The 1 Bed Room - Mental Health may vary in configuration to suit different Ensuite options including: - 1 BR-MH-A Inboard Ensuite - 1 BR-MH-B Shared Ensuite, access from corridor - 1 BR-MH-C Back-to-Back Ensuites Additional Design Considerations: - Fittings and Furniture: . removable drawers must not to be installed . if hooks are required, they must be collapsible with a breaking strain of not more than 15kg - Door & Joinery Hardware . door hardware and joinery hardware must not provide ligature points -Windows and frames . windows must comply with relevant glazing safety standards . window frames must ensure that glazing will stay in place in the event of an attack; the window must prevent escape after being broken Acoustics: Acoustic privacy is required. Body Protected Electrical Area
Amendment 20.07.2011 First Draft 14.10.2015 Description, FF modified 26.06.2023 RDS reviewed
ID Fabric Material Finish Specification Selection Remarks
7001 Windows natural light & outlook essential
3067 Wall finish Laminate Prefinished for TV where required
1144 Floor finish Carpet Synthetic Carpet tiles cushioned vinyl also acceptable
3092 Wall protection MDF Laminate Bed protection wall panel
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
1088 Skirting Timber Paint 150mmH x 20mm thick nominal MDF also acceptable; or floor vinyl coved skirting if vinyl is used
2767 Cornice Plasterboard Paint Square set
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 1200mm clear inward & outward opening; lockable; glazing with integral venetians, control to corridor side
ID Description Category Group Qty Selection / Remarks
690 Bed: domestic, single Furniture/ Fitting 3 1
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to external window & door glazing
2150 Chair: patient Furniture/ Fitting 3 1 suitable for mental health use
2655 Chair: visitor Furniture/ Fitting 3 1 suitable for mental health use
4330 Cupboard: wardrobe Furniture/ Fitting 1 1 with shelves and collapsable hanging rail
5910 Desk: built in Furniture/ Fitting 1 1 laminate
8322 Locker: bedside MEQ - Furniture 3 1 heavy or fixed to wall; drawers must not be removable
13730 Mirror: acrylic Metalwork 1 1 optional; may also use safety glass mirror
23410 Bracket: television, wall mount Metalwork 2 1 vandal proof, optional
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional; if provided TV should be inside a recessed vandal proof cabinet
ID Description Service Category Qty Selection / Remarks
9040 Body protected Power
2576 PO: Cleaner Power 1
2582 PO: Single Power 4 2 to each side of bed
2582 PO: Single Power 2 1 - over desk; 1 - TV (optional)
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8000 Patient to Staff call Nurse Call 1 + indicator button & light
6060 Special: night lights Lighting vandal proof
5000 Airconditioning HVAC with vandal proof outlet
2559 IPTV Communications 1
8080 Emergency call Nurse Call 1 + indicator button & light; may be a duress call system
2738 General LED: vandal proof Lighting
1087 Special: reading, vandal proof Lighting 1 may be ceiling recessed