Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 |
Online Room Data Sheet |
---|
Room Code | PBTR-RS1-12-I |
Net Room Area Briefed | 12 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1 staff |
Description / Special Requirements | A Patient Bed Bay used for the recovery of patients from anaesthetic, located within the Operating Unit or Day Procedures Unit. A clinical handwashing basin will be provided for each 4 Recovery Bed Bays. Recovery Bed Bays will require direct observation from the Staff Station. Recovery Bed Bays for Male and Female Patients shall be separated into two zones by means of physical separation. Visual connection between the two zones shall be avoided. Cardiac Protected electrical area |
Amendment | 24.10.10, - First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
3092 | Wall protection | MDF | Laminate | Bed protection wall panel | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
7001 | Windows | Desirable | ||||
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
150 | Air flowmeter | Furniture/ Fitting | 3 | 1 | |
700 | Bed: inpatient, manual | Furniture/ Fitting | 3 | 1 | |
1252 | Blind: Venetian integral | Furniture/ Fitting | 1 | 1 | to external window/s |
1465 | Bracket: suction bottle | Furniture/ Fitting | 2 | 2 | |
1470 | Bracket: sharps | Furniture/ Fitting | 2 | 1 | |
4600 | Curtain track: bed screen | Metalwork | 1 | 1 | |
5000 | Curtain: bed screen | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
12900 | Louvred panel: for storage-bins | Metalwork | 1 | 1 | optional |
15100 | Bracket: monitor | Furniture/ Fitting | 3 | 1 | |
16250 | Oxygen flowmeter | Furniture/ Fitting | 3 | 2 | |
19700 | Sharps bin | Furniture/ Fitting | 3 | 1 | |
19800 | Shelf: laminate | Furniture/ Fitting | 1 | 1 | to bedhead, full length |
21755 | Storage bins | Furniture/ Fitting | 3 | 3 | to louvred panel, if provided |
21950 | Suction adapter | Furniture/ Fitting | 3 | 2 | |
22000 | Suction bottle | Furniture/ Fitting | 3 | 2 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
31700 | Light: examination, ceiling | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
36050 | Monitor: cardiac | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | on bracket |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 1 | services panel |
1120 | Monitor connection facilities and cabling | Communications | 1 | optional, if networked monitoring required |
5000 | Airconditioning | HVAC | ||
6001 | General: colour corrected | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 2 | services panel |
7020 | Medical Air (MA) | Medical Gases | 1 | services panel |
7040 | Suction | Medical Gases | 3 | services panel |
8000 | Patient/ Staff call | Nurse Call | 1 | + indicator button & light |
8005 | Patient call handset | Nurse Call | 1 | call button on the handset |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
9000 | GPO: Single | Power | 3 | services panel |
9010 | GPO: Emergency power, single | Power | 4 | 3-services panel, 1 for monitor, if required |
9015 | GPO: Cleaner | Power | 1 | may serve a group of beds |
9030 | Cardiac protected/ IPS | Power | ||
9060 | GPO: Special: for equipment | Power | 1 | exam light |
11000 | Wall panel | Services Panels | 1 |