An enclosed single Bed Bay for patient requiring high level nursing care, observation and medical treatment; Visual access to Staff Station is required; integral venetian or smart glass on internal observation windows are required for patient privacy. Maximum natural light is required to patient beds.
Acoustics: Acoustic privacy is required.
Cardiac Protected Electrical Area
Amendment
11.07.2019 First Draft
13.05.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
1253
Observation
Alum/ Toughened glass
Powdercoat
Internal window, double glazed
with integral venetians; to write-up bay walls
7001
Windows
natural light & outlook desirable
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin
6170
Doors
Alum/ Toughened glass
Powdercoat/ Paint
Triple leaf, fully glazed, sliding
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
2767
Cornice
Plasterboard
Paint
Square set
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1102
Bench: resinate, mobile
Furniture/ Fitting
3
1
optional
1252
Blind: Venetian integral
Furniture/ Fitting
1
3
to internal & external windows; internal observation window, 2-way control; smart glass also acceptable for internal window
2150
Chair: patient
Furniture/ Fitting
3
1
2610
Chair: visitor, stackable
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near entry
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
2
8297
Bracket: suction bottle
MEQ - General
2
2
8306
IV pole: mobile
MEQ - General
3
1
8309
Oxygen flowmeter
MEQ - General
3
2
8318
Suction adapter
MEQ - General
3
2
8321
Suction bottle
MEQ - General
3
2
8322
Locker: bedside
MEQ - Furniture
3
1
mobile, 2 lockable top drawers
8332
Table: overbed
MEQ - Furniture
3
1
8404
Bracket: sharps disposal
MEQ - General
2
1
8593
Bracket: patient monitor
MEQ - General
2
1
8608
Waste bin: clinical, 120 litres
MEQ - Furniture
3
1
8724
Trolley: multi-purpose
MEQ - Furniture
3
1
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
20000
Shelving unit: adjustable
Furniture/ Fitting
1
1
near basin
21700
Stool: adjustable, mobile, high
Furniture/ Fitting
3
1
for staff
23410
Bracket: television, wall mount
Metalwork
2
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
8472
Infusion pump: syringe
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
8734
Bed: inpatient, electric, with foam mattress
3
1
yes
___
___
___
___
___
___
___
8776
Monitor: physiologic, acute care
3
1
yes
yes
___
___
___
___
___
___
8988
Infusion pump: enteral feeding
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
8989
Infusion pump: single channel
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
10132
Clock: master clock
3
1
yes
opt
___
___
___
___
___
___
8542
Light: examination, single, ceiling mounted
1
1
yes
___
___
___
___
___
___
___
optional
15985
Dialysis station
1
1
___
___
yes
___
yes
yes
yes
___
optional; with RO water outlet & tundish drain
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54520
Telephone: handset, handsfree
3
1
___
yes
___
___
___
___
___
___
wall phone
Services
ID
Description
Service Category
Qty
Selection / Remarks
2576
PO: Cleaner
Power
1
as required
2577
PO: Double
Power
1
to bench
8080
Emergency call
Nurse Call
1
+ indicator button & light
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button & light switch on the handset
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light
7040
Suction
Medical Gases
2
patient services panel
7020
Medical Air (MA)
Medical Gases
2
patient services panel
7000
Oxygen (O2)
Medical Gases
2
patient services panel
6060
Special: night lights
Lighting
6050
Special: reading
Lighting
up/ down light
2242
General LED: colour corrected
Lighting
5000
Airconditioning
HVAC
2559
IPTV
Communications
1
1006
Voice / Data outlet: double
Communications
3
2- patient services panel, 1-bench
2724
Direct connection: Emergency power
Power
2
1- sensor operated tapware; 1- exam light
2579
PO: Emergency power, single
Power
6
patient services panel
2582
PO: Single
Power
3