Single bed room which may be used to isolate patients with known infectious conditions; natural light and outlook is essential. Glazing to room front and doors is recommended for patient visibility.
The Isolation Room - Negative Pressure will require an internal staff handwash basin, direct access to ensuite toilet and shower facilities, and an Anteroom or Airlock to maintain air pressurisation.
Acoustics: Acoustic privacy is required.
Body Protected electrical area
Amendment
23.12.2024 First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5007
Ceiling
Plasterboard
Paint
Bulkhead
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500mm AFFL
as required; other heights also acceptable as per project standardisation
3000
Wall finish
Paint
Acrylic, washable
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin; other smooth impervious finish also acceptable
3092
Wall protection
MDF
Laminate
Bed protection wall panel
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
3067
Wall finish
Laminate
Prefinished
wall panels
7001
Windows
natural light & outlook essential
1045
Floor finish
Vinyl, non slip
Textured
Seamless, coved
under basin
2767
Cornice
Plasterboard
Paint
Square set
1253
Observation
Alum/ Toughened glass
Powdercoat
Internal window, double glazed
with integral venetians or intelligent glass; optional
9127
Doors
Solid Core/ Safety glass
Paint
1 1/2 leaf, observation panel
Min. 1350mm clear opening; 1400mm clear opening ideal
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1252
Blind: Venetian integral
Furniture/ Fitting
1
3
to internal & external windows; internal observation window, 2-way control; iGlass can also be used
2150
Chair: patient
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
4330
Cupboard: wardrobe
Furniture/ Fitting
1
1
with shelves and hanging rail
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near entry
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
1
medical air
8297
Bracket: suction bottle
MEQ - General
2
1
8306
IV pole: mobile
MEQ - General
3
1
8309
Oxygen flowmeter
MEQ - General
3
1
8318
Suction adapter
MEQ - General
3
1
8321
Suction bottle
MEQ - General
3
1
8322
Locker: bedside
MEQ - Furniture
3
1
mobile, 2 lockable top drawers
8332
Table: overbed
MEQ - Furniture
3
1
23410
Bracket: television, wall mount
Metalwork
2
1
flat screen TV
24102
Waste bin: general
Furniture/ Fitting
3
1
to basin; foot pedal operated
8605
Waste bin: clinical, 20 litres
MEQ - Furniture
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
wall mounted
8734
Bed: inpatient, electric, with foam mattress
3
1
yes
___
___
___
___
___
___
___
8989
Infusion pump: single channel
3
1
yes
opt
___
___
___
___
___
___
optional
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
15985
Dialysis station
1
1
___
___
yes
___
___
yes
yes
___
optional
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
bedhead
2559
IPTV
Communications
1
5000
Airconditioning
HVAC
6050
Special: reading
Lighting
up/ down light
6060
Special: night lights
Lighting
7000
Oxygen (O2)
Medical Gases
1
7020
Medical Air (MA)
Medical Gases
1
7040
Suction
Medical Gases
1
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button & light switch on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2582
PO: Single
Power
4
bedhead
2582
PO: Single
Power
3
1 - at low level for patient bed; 1- at patient chair; 1 - TV