Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
1BR-CCU-20-I
Net Room Area Briefed
20
Hours of Operation
24 Hours
Occupancy
1 patient; 1-2 visitors, 1-2 staff intermittently
Description / Special Requirements
A 1 Bed Room - Special, Coronary Care will accommodate one patient for the delivery of cardiac care treatment. Glazed partition along the corridor wall is recommended for patient visibility and monitoring. Natural light and outlook is essential; the room requires the ability to view out of the window from either the chair or bed. Ensuite is required but should be located on the external wall.
Other design considerations may include:
- ceiilng mounted patient lift for bariatric patients. This should be provided in accordance with the hospital's service plan.
- a minimum number of rooms with provisions for dialysis station are highly recommended but not mandatory. Provisions should be
in accordance with the hospital's service plan.
Acoustics: Acoustic privacy is required.
Body Protected Electrical Area
Amendment
24.10.2010 First Draft
13.04.2011 FF & Services modified
01.06.2016 Revisions to Briefed Area, Description, Fabric, FF, Services
02.05.2023 - RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
3092
Wall protection
MDF
Laminate
Bed protection wall panel
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
3067
Wall finish
Laminate
Prefinished
wall panels
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
1045
Floor finish
Vinyl, non slip
Textured
Seamless, coved
under basin
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
7001
Windows
natural light & outlook essential
1253
Observation
Alum/ Toughened glass
Powdercoat
Internal window, double glazed
with integral venetian
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500mm AFFL
as required; other heights also acceptable as per project standardisation
2767
Cornice
Plasterboard
Paint
Square set
9127
Doors
Solid Core/ Safety glass
Paint
1 1/2 leaf, observation panel
Min. 1350mm clear opening; 1400mm clear opening ideal; latch set
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1252
Blind: Venetian integral
Furniture/ Fitting
1
1
to internal & external windows; internal observation window, 2-way control; roller or vertical blinds also acceptable to external window
2050
Chair: lounge, sofa bed
Furniture/ Fitting
3
1
optional
2150
Chair: patient
Furniture/ Fitting
3
1
2650
Chair: visitor, patient
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
4330
Cupboard: wardrobe
Furniture/ Fitting
1
1
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near basin
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
2
8297
Bracket: suction bottle
MEQ - General
2
4
8309
Oxygen flowmeter
MEQ - General
3
4
8318
Suction adapter
MEQ - General
3
4
8321
Suction bottle
MEQ - General
3
4
8322
Locker: bedside
MEQ - Furniture
3
1
8332
Table: overbed
MEQ - Furniture
3
1
8404
Bracket: sharps disposal
MEQ - General
2
1
8593
Bracket: patient monitor
MEQ - General
2
1
8594
Linen carrier: dirty, single
MEQ - Furniture
3
1
8608
Waste bin: clinical, 120 litres
MEQ - Furniture
3
1
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
19800
Shelf: laminate
Furniture/ Fitting
1
1
for flowers
23410
Bracket: television, wall mount
Metalwork
2
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
8472
Infusion pump: syringe
3
1
yes
opt
___
___
___
___
___
___
optional, Qty TBC by project
8989
Infusion pump: single channel
3
1
yes
opt
___
___
___
___
___
___
optional, Qty TBC by project
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
8733
Bed: ICU, electric
3
1
yes
opt
___
___
___
___
___
___
8988
Infusion pump: enteral feeding
3
1
yes
opt
___
___
___
___
___
___
optional, Qty TBC by project
8485
Monitor: physiologic, critical care
3
1
yes
yes
___
___
___
___
___
___
8788
Supply unit: ceiling, tandem, double arm
2
1
yes
yes
___
___
___
___
___
___
optional, may be replaced with wall service panel depending on operational requirements
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
2
2- patient services pendant
2559
IPTV
Communications
1
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
6050
Special: reading
Lighting
up/ down light
6060
Special: night lights
Lighting
7000
Oxygen (O2)
Medical Gases
4
to patient services pendant
7020
Medical Air (MA)
Medical Gases
2
to patient services pendant
7040
Suction
Medical Gases
4
to patient services pendant
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button & light switch on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2582
PO: Single
Power
3
1 - for patient chair; 1 - TV; 1 - at low level for patient bed
2579
PO: Emergency power, single
Power
6
to patient services pendant
2576
PO: Cleaner
Power
1
as required
2724
Direct connection: Emergency power
Power
2
1- sensor operated tapware; 1- patient services pendant
1412
Special: examination downlight
Lighting
over bed
1005
Voice / Data outlet: single
Communications
1
to telephone
2723
PO: Cardiac Protected/IPS, single
Power
8
to patient services pendant
2506
Cardiac protected/ Isolated power
Power
1
2761
Direct connection: Tool Air
Medical Gases
1
to pendant (for brakes)