A 2 Bed Room for general mental health patients; natural light and outlook is essential; The room is to be internally lockable with a master keyed lock from the outside; All fittings are to have a breaking strain of not more than 15kg. All glazing (including external windows) is to comply with standards for Mental Health Facilities.
The 2 Bed Room - Mental Health may vary in configuration to suit different Ensuite options including:
- 2 BR-MH-A-U Inboard Ensuite
- 2 BR-MH-B-U Shared Ensuite with access off the corridor
- 2 BR-MH-D-U Back to Back Ensuites
Acoustics: Acoustic privacy is required.
Body Protected Electrical Area
Amendment
24.10.2010 First Draft
22.02.2016 Document review
20.01.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
7001
Windows
natural light & outlook essential
3000
Wall finish
Paint
Acrylic, washable
1144
Floor finish
Carpet
Synthetic
Carpet tiles
vinyl also acceptable
9006
Doors
Solid Core/ Safety glass
Paint
Single leaf, observation panel
1200mm clear inward & outward opening, lockable
3092
Wall protection
MDF
Laminate
Bed protection wall panel
5007
Ceiling
Plasterboard
Paint
Bulkhead
above wardrobes
2767
Cornice
Plasterboard
Paint
Square set
1088
Skirting
Timber
Paint
150mmH x 20mm thick nominal
MDF also acceptable; or floor vinyl coved skirting if vinyl is used
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
690
Bed: domestic, single
Furniture/ Fitting
3
2
1252
Blind: Venetian integral
Furniture/ Fitting
1
2
to external window & door glazing
2150
Chair: patient
Furniture/ Fitting
3
2
suitable for mental health use
2655
Chair: visitor
Furniture/ Fitting
3
2
suitable for mental health use
4330
Cupboard: wardrobe
Furniture/ Fitting
1
2
with shelves and collapsible hanging rail
5910
Desk: built in
Furniture/ Fitting
1
2
laminate
8322
Locker: bedside
MEQ - Furniture
3
2
heavy or fixed to wall; drawers must not be removable
13730
Mirror: acrylic
Metalwork
1
1
optional; may also use safety glass mirror
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
Services
ID
Description
Service Category
Qty
Selection / Remarks
2576
PO: Cleaner
Power
1
2582
PO: Single
Power
11
4 per bed at bedhead; 1 per desk; 1 - on wall, vandal proof