The After Hours Drug Store is a secure room for the storage of drugs and medications required after hours, accessible only by authorised personnel. Refrigerated storage will be required for some medications. The Store may be replenished by Pharmacy personnel with access from within the Pharmacy or accessed externally by authorised personnel. Room to be lockable both sides.
Automated medication management systems may be installed according to manufacturers specifications.
Storage solutions to meet project specific service, functionality and Work Health and Safety demands. This includes, but is not limited to proprietary storage systems.
Amendment
24.10.2010 First Draft
16.10.2015 Description, FF, FE and Services modified
22.03.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
9001
Doors
Solid Core
Paint
Single leaf
from adjacent Pharmacy; 920mm clear opening, lockable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
9001
Doors
Solid Core
Paint
Single leaf
from corridor; 920mm clear opening, lockable
3000
Wall finish
Paint
Acrylic, washable
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2767
Cornice
Plasterboard
Paint
Square set
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
4420
Cupboard: under bench, lockable
Furniture/ Fitting
1
1
optional; with adjustable shelves
5612
Cabinet: pharmacy management system, full height
Furniture/ Fitting
3
1
optional; freestanding, lockable
20000
Shelving unit: adjustable
Furniture/ Fitting
1
1
optional; over bench
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
9056
Refrigerator: drugs, under-bench, 150L
3
1
yes
yes
___
___
___
___
___
___
with optional freezer, under bench; size depends on operational policy and functional requirement; with built-in temperature monitor and alarm
8710
Medication dispensing system: automated, main unit
2
yes
yes
___
___
___
___
___
___
optional; number of units depend on operational policy