1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code AIRLE-12-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy N/A
Description / Special Requirements Airlock associated with a Main Entry Area for wind/ weather protection and to maintain air pressurisation. It will be used by a wide range of people including fully ambulant, persons using a variety of walking aids, persons in wheelchairs or on trolleys and the general public. The floor finish should be able to catch dirt from footwear or wheelchairs/ trolleys and should be easily cleaned. Sufficient lighting is to be provided. The size of the airlock should allow for several people to enter before the second door opens and should reflect the level of service provision. Entry doors may be glazed and automatic. Walls may also be glazed. 'After-hours' access may require intercom or special security provisions.
Amendment 24.10.2010 First Draft. 20.04.2015 Room Description, Fabric, FFE and Services modified. 28.08.2016 Fabrics & Services updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved default = vinyl, or other suitable slip resistant floor finish
3000 Wall finish Paint Acrylic, washable
2015 Skirting skirting to suit built fabric
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
1150 Floor finish Composite Slip resistant Floor mat, recessed optional; attention to detailing of recessed mat to avoid trip hazard; full floor mat recommended if provided
5007 Ceiling Plasterboard Paint Bulkhead to conceal automatic door mechanisms
2975 Doors Alum framed, safety glass & glazed Powder Coat Sliding door 1800mm clear opening, may be automatic, lockable
6025 Cornice Aluminium Powdercoat shadow line
7003 Windows Aluminium Framed Powder Coated Clear Glazed full height; safety glass

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1000 Bench seat Furniture/ Fitting 1 1 optional, timber/ hardwood with steel frame

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
7300 Camera: CCTV security 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional

Services

ID Description Service Category Qty Selection / Remarks
1035 Door buzzer Communications 1 optional
1100 TV: CCTV Communications 1 optional
5000 Airconditioning HVAC
2576 PO: Cleaner Power 1
10020 Card access Security 1 optional; swipe card access
1438 Emergency door release Security 1
2275 Video intercom Communications 1 optional
9050 Direct connection Power 5 optional 1 - for video intercom, 1 - for CCTV camera, 1 - card access, 2 - for automatic doors
1983 General fluorescent: downlights Lighting