1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code ANWM-I
Net Room Area Briefed 15
Hours of Operation Available 24 Hours
Occupancy 2 - 3
Description / Special Requirements The Anaesthetic Workroom provides an area for the repair, maintenance and calibration of anaesthetic and biomedical equipment, in the Operating Unit. The room may also serve as a work base for anaesthetic and biomedical technicians visiting the Unit. The room will be accessible from both the sterile areas and the non-sterile areas of the Operating Unit.
Amendment 24.10.2010 First Draft 25.06.2022 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 1400mm clear opening
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin & above bench, vinyl or other smooth impervious finish also acceptable
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm set plasterboard also acceptable
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
8040 Door protection Composite Prefinished PVC To door frame
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 900AFFL
1950 Chair: ergonomic, high Furniture/ Fitting 3 2
4420 Cupboard: under bench, lockable Furniture/ Fitting 1 1
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 1 over bench
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
54510 Telephone: handset, standard 3 2 ___ yes ___ ___ ___ ___ ___ ___
9116 Analyser/ tester: electrical safety, automated 3 1 yes opt ___ ___ ___ ___ ___ ___
9117 Analyser/ tester: gas flow 3 1 yes opt ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 6
5005 Air conditioning: special HVAC positive pressure, filtered
2189 General LED Lighting
6055 Special: task light, built in Lighting under O/H cupboards
7000 Oxygen (O2) Medical Gases 1 for testing/ calibrating equipment
7010 Nitrous Oxide (N2O) Medical Gases 1 for testing/ calibrating equipment
7040 Suction Medical Gases 1 for testing/ calibrating equipment
7070 Scavenge Medical Gases 1 for testing/ calibrating equipment
2577 PO: Double Power 5
2724 Direct connection: Emergency power Power 1 sensor operated tapware
2578 PO: Emergency power, double Power 3
11000 Wall panel Services Panels 1 flush mounted
7020 Medical Air (MA) Medical Gases 1 for testing/ calibrating equipment (MA4)
6870 Surgical Air (SA7) Medical Gases 1 for testing/ calibrating equipment, optional