Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
ANCRT-I
Net Room Area Briefed
14
Hours of Operation
Available 24 Hours
Occupancy
Up to 3 staff
Description / Special Requirements
Room adjacent to Angiography Procedure Room/s with direct visibility to the patient for remote control of equipment, and review and reporting of procedure images. The Control/ Reporting room may serve two procedure rooms.
Acoustics: Acoustic privacy is required
Additional Design Considerations:
- Radiation shielding as advised by Radiation Consultant
- Cable ducts from Angiography Procedure Room and Computer/Equipment
room may be required
Amendment
24.10.10, - First Draft
21.04.11, - Services modified
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
5060
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x1200
6025
Cornice
Aluminium
Powdercoat
shadow line
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
7025
Observation
Lead glass
Clear
Internal window
to procedure room
8000
Door protection
Vinyl
Prefinished
Kickplate, 300mm high
9004
Doors
Solid Core/ Glass
Paint
Single leaf, observation panel
920mm clear opening
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
at 900H
1950
Chair: ergonomic, high
Furniture/ Fitting
3
3
3400
Coathook
Metalwork
1
2
17252
Pedestal drawer unit: mobile, 840mmH
Furniture/ Fitting
3
1
under bench
17360
Pinboard: fabric covered
Furniture/ Fitting
1
2
over bench
20000
Shelving unit: adjustable
Furniture/ Fitting
1
2
for books, manuals, over bench
24400
Whiteboard
Furniture/ Fitting
2
1
optional
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
11400
Computer: PC & monitor
3
1
yes
yes
___
___
___
___
___
___
41100
Printer: networked
3
1
yes
yes
___
___
___
___
___
___
54510
Telephone: handset, standard
3
2
___
yes
___
___
___
___
___
___
on bench
62150
IMG: console, control
1
1
yes
yes
___
___
___
___
___
___
Angiography control monitors
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
5
3 outlets under bench for telephone
1040
Intercom
Communications
1
with handsfree microphone to Angio room
5000
Airconditioning
HVAC
6000
General fluorescent
Lighting
6055
Special: task light, built in
Lighting
under O/H shelving
9001
GPO: Double
Power
8
9015
GPO: Cleaner
Power
1
9060
GPO: Special: for equipment
Power
1
Angiography console equipment