Room adjacent to Angiography Procedure Room/s with direct visibility to the patient for remote control of equipment, and review and reporting of procedure images. The Control/ Reporting room may serve two procedure rooms.
Acoustics: Acoustic privacy is required
Additional Design Considerations:
- Radiation shielding as advised by Radiation Consultant
- Cable ducts from Angiography Procedure Room and Computer/Equipment
room may be required
Amendment
24.10.2010 First Draft
21.04.2011 Services modified
22.02.2022 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
1219
Door Protection
Composite
Prefinished PVC
Kickplate, 300mm high
9001
Doors
Solid Core
Paint
Single leaf
920mm clear opening
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
7025
Observation
Lead glass
Clear
Internal window
to procedure room
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
at 900H
1950
Chair: ergonomic, high
Furniture/ Fitting
3
3
3400
Coathook
Metalwork
1
2
17252
Pedestal drawer unit: mobile, 840mmH
Furniture/ Fitting
3
1
under bench
20000
Shelving unit: adjustable
Furniture/ Fitting
1
2
for books, manuals, over bench
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
11400
Computer: PC & monitor
3
1
yes
yes
___
___
___
___
___
___
41100
Printer: networked
3
1
yes
yes
___
___
___
___
___
___
54510
Telephone: handset, standard
3
2
___
yes
___
___
___
___
___
___
on bench
9092
Control console
2
yes
yes
___
___
___
___
___
___
part of angiography unit
Services
ID
Description
Service Category
Qty
Selection / Remarks
2576
PO: Cleaner
Power
1
6055
Special: task light, built in
Lighting
under O/H shelving
2189
General LED
Lighting
5000
Airconditioning
HVAC
1040
Intercom
Communications
1
with handsfree microphone to Angio room
1006
Voice / Data outlet: double
Communications
4
to control console and computers
6076
Special: 'X-ray In Use' lights
Lighting
1
2578
PO: Emergency power, double
Power
1
to wall
2726
PO: UPS, double
Power
8
to control console and computers
12011
Radiation shielding
Shielding
1
to wall, door & glazing shared with angiography procedure room as specified by Radiation Consultant