Room Code | ANPR-I |
Net Room Area Briefed | 42 |
Hours of Operation | Available 24 Hours |
Occupancy | 1 patient, up to 6 staff |
Description / Special Requirements | Procedure room where Angiography procedures and electrophysiology studies are undertaken in a controlled environment. A Control room will be located adjacent and may serve more than one procedure room. A clinical scrub area should be located immediately adjacent to the room staff entry. Acoustics: Acoustic privacy is required Cardiac Protected Electrical Area Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Unistrut Ceiling able to carry moving loads may be required - Cable ducts from Control Room and Computer/Equipment room may be required - 'X-Ray in Use' lights are required outside each entry door - Power to Angiography equipment should be on emergency supply |
Amendment | 24.10.2010 First Draft 21.04.2011 Services modified 20.02.2023 RDS reviewed |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | at 3000 mm AFFL | |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9005 | Doors | Solid Core/ Lead glass | Paint | Single leaf, observation panel, lead shielding | staff entry/ exit | |
7025 | Observation | Lead glass | Clear | Internal window | to control room | |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
4020 | Wall protection | Composite | Prefinished PVC | Crash rail at 900mm AFFL | ||
2767 | Cornice | Plasterboard | Paint | Square set | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
9130 | Doors | Solid Core | Paint | 1 1/2 leaf, with lead shielding | patient entry/ exit, 1600mm clear opening |
ID | Description | Category | Group | Qty | Selection / Remarks |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | adjustable shelves |
4430 | Cupboard: drawer unit | Furniture/ Fitting | 1 | 1 | under bench |
4493 | Cupboard: catheter hanging | Furniture/ Fitting | 1 | 1 | sliding glass doors, shelving to one side |
24105 | Waste bin: fliptop, 20 Litre | Furniture/ Fitting | 3 | 1 | under bench |
8291 | Air flowmeter | MEQ - General | 3 | 1 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 2 | services panel |
8297 | Bracket: suction bottle | MEQ - General | 2 | 2 | |
8318 | Suction adapter | MEQ - General | 3 | 2 | |
8321 | Suction bottle | MEQ - General | 3 | 2 | on bracket |
8404 | Bracket: sharps disposal | MEQ - General | 2 | 1 | |
8306 | IV pole: mobile | MEQ - General | 3 | 1 | |
8313 | Rack: lead apron | MEQ - Imaging | 1 | 1 | |
21680 | Stool: adjustable, mobile | Furniture/ Fitting | 3 | 2 | |
8630 | Table: mayo | MEQ - Furniture | 3 | 1 | |
8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
8620 | Trolley: instrument | MEQ - Furniture | 3 | 1 | |
8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
8405 | Sharps disposal: wall mounted, 11L | MEQ - General | 2 | 1 | |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 1 | |
8608 | Waste bin: clinical, 120 litres | MEQ - Furniture | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
10132 | Clock: master clock | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
9428 | Injector: contrast media, mobile, single head, angiography | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | or ceiling mounted injector |
9556 | Supply dispensing system: automated, catheter, main unit | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional depending on operational requirements |
9557 | Supply dispensing system: automated, catheter, auxiliary | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional depending on operational requirements |
8559 | Angiography: interventional radiology, single plane, ceiling mounted | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | single plane or bi-plane, ceiling mounted or floor mounted depending on operational requirements |
8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
8982 | Light: surgical, single, ceiling, with camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | with (optional) camera |
9056 | Refrigerator: drugs, under-bench, 150L | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
9101 | Angiography table | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 4 | 1- bench; 2- patient services pendant; 1- wall |
1040 | Intercom | Communications | 1 | handsfree to control room |
5000 | Airconditioning | HVAC | ||
6001 | General: colour corrected | Lighting | ||
6110 | Downlights: dimmable | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 2 | patient services pendant |
7010 | Nitrous Oxide (N2O) | Medical Gases | 1 | patient services pendant |
7020 | Medical Air (MA) | Medical Gases | 1 | patient services pendant |
7040 | Suction | Medical Gases | 2 | patient services pendant |
7070 | Scavenge | Medical Gases | 1 | patient services pendant |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
2579 | PO: Emergency power, single | Power | 6 | to patient services pendant |
2578 | PO: Emergency power, double | Power | 7 | 2 above bench; 3- wall; 1- under bench refrigerator; 1- resuscitation equipment |
2576 | PO: Cleaner | Power | 1 | |
9030 | Cardiac protected/ IPS | Power | ||
12030 | Lead lining | Shielding | to walls and doors as specified | |
1005 | Voice / Data outlet: single | Communications | 3 | 1- under bench refrigerator; 2- supply automated dispensing units |
6076 | Special: 'X-ray In Use' lights | Lighting | 1 | |
2234 | Direct connection: Uninterrupted power | Power | 1 | to operating light |
11505 | Floor duct for power & data | Services Ducts | 1 | between equipment room, control room, and scanning room |
2682 | PO: Double, UPS (uninterruptible power) | Power | 2 | 2- supply dispensing units |
2556 | Trunking: 200mm x 70mm | Electrical Installations | 1 | between equipment room, control room, and scanning room |
2190 | Air pressure monitoring device | HVAC | 1 | |
5040 | Pressure: positive | HVAC | 1 | |
2723 | PO: Cardiac Protected/IPS, single | Power | 6 | to patient services pendant |
2761 | Direct connection: Tool Air | Medical Gases | 1 | to patient services pendant (for brakes) |
2724 | Direct connection: Emergency power | Power | 1 | to patient services pendant |
2760 | Direct connection: Voice/ Data | Communications | 1 | operating light camera attachment (optional) |