The Aseptic Room is a clean room designed for sterile medication manufacturing, including intravenous fluid. The room should maintain positive relative pressure and must be accessed via an Anteroom and airlock.
Body Protected electrical area
Design Considerations include:
- Electronic interlock door system should be provided to prevent the opening of both doors in the Anteroom at the same time
- Handwashing facilities should be provided immediately outside the Aseptic (Clean) Rooms in the adjoining Anteroom. Hand basins are not to be located within the Aseptic (Clean) Rooms
- An intercom system should be provided between Aseptic (Clean) Room and Anteroom
- High-resolution CCTV cameras for remote monitoring should be provided
- The facility must comply with the room requirements set forth in relevant International Clean Room standards for sterile manufacturing
- Work benches are to be freestanding and in stainless steel. Stainless steel trolleys can be provided for minimal storage
Amendment
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
1708
Doors
Solid Core
Laminate
Single leaf
920mm clear opening
5025
Ceiling
Plasterboard
Paint, epoxy
Flush set, suspended
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2-coat epoxy paint also acceptable
3000
Wall finish
Paint
Acrylic, washable
2-coat epoxy paint also acceptable
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
2-coat epoxy paint also acceptable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
24101
Waste bin: 120 Litre
Furniture/ Fitting
3
1
stainless steel
8629
Trolley: SS, multi-purpose
MEQ - Furniture
3
1
9007
Stool: adjustable, mobile, high, with backrest
Furniture/ Fitting
3
1
9101
Hatch: pass-through
MEQ - Pharmacy
2
1
8873
Shelving: stainless steel, wire mesh, mobile
MEQ - Sterilisation
3
1
1010
Bench: stainless steel
Metalwork
1
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
5855
Clock: electric
1
1
yes
___
___
___
___
___
___
___
8859
Laminar flow hood: horizontal, 1200mm
2
2
yes
___
___
___
___
___
___
___
quantity may change based on operational requirements