Bay - Mobile Equipment, 10m2

Room Code BMEQ-10-I
Net Room Area Briefed 10
Hours of Operation 24 Hours
Occupancy N/A
Description / Special Requirements An open storage bay for parking mobile equipment which may include patient beds, wheelchairs trolleys or other mobile equipment. The parking area may be used for equipment waiting for repair, returning from repair or surplus equipment. Special Design Requirements: The Bay should be deep enough to ensure equipment stored does not impede corridor circulation. Electrical equipment that requires recharging may be stored in this space whilst recharging, therefore provision of appropriately located power outlets will be required.
Amendment 24.10.10, - First Draft

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
4020 Wall protection Composite Prefinished PVC Crash rail at 900 AFFL
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6025 Cornice Aluminium Powdercoat shadow line
4031 Wall protection Composite Prefinished PVC Corner guards to 1500 AFFL

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
700 Bed: inpatient, manual Furniture/ Fitting 3 1 as required
23950 Trolley Furniture/ Fitting 3 1 as required
24200 Wheelchair Furniture/ Fitting 3 2 as required

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks

Services

ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
2189 General LED Lighting
2577 PO: Double Power 2 For recharging of electrical equipment