An open storage bay for one or more items of mobile equipment in frequent use which may include wheelchairs, mobile scales, commode chairs, patient lifting devices or other mobile equipment.
Special Design Requirements: The Bay should be deep enough to ensure equipment stored does not impede corridor circulation; bay depth 800 -1200mm depending on equipment to be stored.
If the the bay is used to store equipment that requires recharging, appropriate power outlets should be provided.
Amendment
24.10.2010 First Draft
02.09.2014 FF amended
28.10.2014 FF modified
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
or consistent with adjacent area
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
or consistent with adjacent area
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900mm AFFL
4022
Wall protection
Composite
Prefinished PVC
Crash rail at 350mm AFFL
optional
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500mm AFFL
other heights also acceptable as per project standardisation