1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code BPATH-1-I
Net Room Area Briefed 1
Hours of Operation 24 Hours
Occupancy 1
Description / Special Requirements A Pathology Bay provides an area for the preparation and holding of patient specimens. May include processing of patient specimens. The bay may be located in Critical Care Units or Pre-Operative and Post-Operative areas.
Amendment 24.10.2010 First Draft. 22.04.2015 Room Name, Room Code, Fabric & FF modified.

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL other heights also acceptable as per project standardisation
3060 Wall finish Vinyl Prefinished Splashback to sink, other smooth impervious finish also acceptable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended or consistent with adjacent area
5007 Ceiling Plasterboard Paint Bulkhead
2767 Cornice Plasterboard Paint Square set or consistent with adjacent area
3000 Wall finish Paint Acrylic, washable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 with inset sink
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 1 over bench
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to sink
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to sink
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1 under bench, optional
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ to bench, optional

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1
5000 Airconditioning HVAC consistent with adjacent area
2189 General LED Lighting consistent with adjacent area
6055 Special: task light, built in Lighting under O/H cupboards
2582 PO: Single Power 1
2579 PO: Emergency power, single Power 1