The Utility Bay provides an area with a bench and sink for use as a preparation area. The bay may be located adjacent to patient treatment areas. The bay should be located in close proximity to a staff handwashing basin.
Amendment
24.10.2010 First Draft
06.05.2011 Room Fabric updated
18.08.2016 Services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500mm AFFL
other heights also acceptable as per project standardisation
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
3000
Wall finish
Paint
Acrylic, washable
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
minimum height 2400mm; or consistent with adjacent area
2767
Cornice
Plasterboard
Paint
Square set
or consistent with adjacent area
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1010
Bench: stainless steel
Metalwork
1
1
with wet edge and inset sink, open under
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to sink
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
20000
Shelving unit: adjustable
Furniture/ Fitting
1
1
over bench
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
4045
Tapware: elbow mixer
1
1
___
___
yes
yes
yes
___
___
___