The Bone Densitometry rooms is an X-ray room for undertaking bone denistometry radiographic procedures, located within the Imaging Unit.
Additional Design Requirements:
- Radiation sheilding to walls and glazing as advised by Radiation Consultant
- Cable ducting between the X-ray table, vertical bucky and control area may be
required, depending on equipment type and layout
- 'X-ray in Use' warning lights will be required outside each entry door
Body Protected electrical area
Amendment
12.02.2024 First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
9230
Doors
Solid Core
Paint
Double leaf, with lead shielding
patient entry/ exit; 1400mm (min) clear opening
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500mm AFFL
other heights also acceptable as per project standardisation
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150 mmH
8040
Door protection
Composite
Prefinished PVC
To door frame
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
at 3000mm AFFL
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
2150
Chair: patient
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
1
8297
Bracket: suction bottle
MEQ - General
2
1
8309
Oxygen flowmeter
MEQ - General
3
1
8318
Suction adapter
MEQ - General
3
1
8321
Suction bottle
MEQ - General
3
1
8635
Lead screen: mobile
MEQ - Imaging
3
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
wall telephone
9042
Bone densitometer: DEXA
3
1
yes
yes
___
___
___
___
___
___
with workstation
8919
Scale: patient, with stadiometer
3
1
yes
___
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
12011
Radiation shielding
Shielding
to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
2724
Direct connection: Emergency power
Power
1
sensor tap
9040
Body protected
Power
2579
PO: Emergency power, single
Power
2
to patient services panel
2577
PO: Double
Power
2
to walls
8080
Emergency call
Nurse Call
1
+ indicator button & light
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
7040
Suction
Medical Gases
1
patient services panel
7020
Medical Air (MA)
Medical Gases
1
patient services panel
7000
Oxygen (O2)
Medical Gases
1
patient services panel
2467
Downlights: LED
Lighting
2242
General LED: colour corrected
Lighting
5000
Airconditioning
HVAC
1006
Voice / Data outlet: double
Communications
2
1- patient services panel; 1- bone densitometer workstation
1005
Voice / Data outlet: single
Communications
2
1- bone densitometer scanner; 1- wall telephone
6005
Dimmable
Lighting
2726
PO: UPS, double
Power
2
to bone densitometer workstation/ printer
2694
PO: UPS, single
Power
1
to bone densitometer scanner according to manufacturer's recommendations