X-ray Room for CT scanning procedures with an adjacent Control Room and Computer Room. The Control Room may serve more than one CT Scanning Room
Acoustics: Acoustic privacy is required
Body Protected electrical area
Additional Design Considerations:
- Radiation shielding as advised by Radiation Consultant
- Metal tracks on ceiling able to carry moving loads may be required
- Cable ducts between Control Room and Computer Room may be
required
- 'X-ray in Use' lights are required outside each entry door
- Power should be on emergency supply
Amendment
24.10.2010 First Draft
05.05.2011 FF modified
28.05.2014 General amendments to services
20.01.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
8040
Door protection
Composite
Prefinished PVC
To door frame
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900mm AFFL
7025
Observation
Lead glass
Clear
Internal window
to control room
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
9005
Doors
Solid Core/ Lead glass
Paint
Single leaf, observation panel, lead shielding
staff entry; sliding panel to observation window
2767
Cornice
Plasterboard
Paint
Square set
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
at 3000 mm AFFL
9130
Doors
Solid Core
Paint
1 1/2 leaf, with lead shielding
patient entry/ exit 1600mm clear opening
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
4345
Cupboard: sliding doors, adj shelves
Furniture/ Fitting
3
1
with glass sliding doors; optional
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near door
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
1
8297
Bracket: suction bottle
MEQ - General
2
2
8309
Oxygen flowmeter
MEQ - General
3
2
8318
Suction adapter
MEQ - General
3
2
8321
Suction bottle
MEQ - General
3
2
8313
Rack: lead apron
MEQ - Imaging
1
1
1030
Bench: resinate
Furniture/ Fitting
1
1
8402
Footstool: 2-step
MEQ - Furniture
3
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
8620
Trolley: instrument
MEQ - Furniture
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
7300
Camera: CCTV security
1
yes
___
___
___
___
___
___
___
part of CT scanning system configurations
9109
Injector: contrast media, mobile, dual head, CT
3
1
yes
yes
___
___
___
___
___
___
9083
Scanning unit: CT, 128-slice
2
1
yes
yes
___
___
___
___
___
___
number of slices will change according to project's requirements
8782
Monitor: physiologic, vital signs, on stand
3
1
yes
opt
___
___
___
___
___
___
optional
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
3
1- patient services panel; 1- bench; 1- wall
1040
Intercom
Communications
1
speakers and mic are mounted on the grantry
5000
Airconditioning
HVAC
2189
General LED
Lighting
6005
Dimmable
Lighting
7000
Oxygen (O2)
Medical Gases
2
patient services panel
7010
Nitrous Oxide (N2O)
Medical Gases
1
patient services panel
7020
Medical Air (MA)
Medical Gases
1
patient services panel
7040
Suction
Medical Gases
2
patient services panel
7070
Scavenge
Medical Gases
1
patient services panel
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2579
PO: Emergency power, single
Power
4
to patient services panels
2578
PO: Emergency power, double
Power
4
to walls (including injector)
2576
PO: Cleaner
Power
1
9040
Body protected
Power
11000
Wall panel
Services Panels
1
flush mounted
12011
Radiation shielding
Shielding
to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
2724
Direct connection: Emergency power
Power
1
sensor operated tapware
1080
Clock: master clock
Communications
1
battery/ POE/ electrical connection TBC
2556
Trunking: 200mm x 70mm
Electrical Installations
1
between scanning room, control room, and equipment room
6076
Special: 'X-ray In Use' lights
Lighting
1
2502
Clean Agent Gas Suppression System
Fire Services
1
4030
Drainage
Hydraulics
1
for safety drain through sink (if water condenses from gantry), optional depending on manufacturer's specifications
2577
PO: Double
Power
1
to bench
11505
Floor duct for power & data
Services Ducts
1
between scanning room, control room, and equipment room