| Room Code | CLAB-60-I |
| Net Room Area Briefed | 60 |
| Hours of Operation | Available 24 Hours |
| Occupancy | 1 patient, up to 6 staff |
| Description / Special Requirements | Procedure room where Cardiac Catheter procedures and electrophysiology studies are undertaken in a controlled environment. A Control room will be located adjacent and may serve more than one procedure room. A clinical scrub area should be located immediately adjacent to the room staff entry. Acoustics: Acoustic privacy is required Cardiac Protected Electrical Area Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Unistrut Ceiling able to carry moving loads may be required - Cable ducts from Control Room and Computer/Equipment room may be required - 'X-Ray in Use' lights are required outside each entry door - Power to Angiography equipment should be on emergency supply |
| Amendment | 23.12.2024 First Draft |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
| 3000 | Wall finish | Paint | Acrylic, washable | |||
| 7025 | Observation | Lead glass | Clear | Internal window | to control room | |
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 9005 | Doors | Solid Core/ Lead glass | Paint | Single leaf, observation panel, lead shielding | staff entry/ exit, 920mm clear opening | |
| 5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
| 9130 | Doors | Solid Core | Paint | 1 1/2 leaf, with lead shielding | patient entry/ exit, 1600mm clear opening | |
| 2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
| 4020 | Wall protection | Composite | Prefinished PVC | Crash rail at 900mm AFFL | ||
| 6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
| 6362 | Doors | Solid Core | Paint | Single leaf, with lead shielding | optional, to equipment room, 1000mm clear opening |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | |
| 4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | adjustable shelves |
| 4430 | Cupboard: drawer unit | Furniture/ Fitting | 1 | 1 | under bench |
| 4493 | Cupboard: catheter hanging | Furniture/ Fitting | 1 | 1 | sliding glass doors, shelving to one side |
| 24105 | Waste bin: fliptop, 20 Litre | Furniture/ Fitting | 3 | 1 | under bench |
| 8291 | Air flowmeter | MEQ - General | 3 | 1 | to patient supply unit |
| 8309 | Oxygen flowmeter | MEQ - General | 3 | 2 | to patient supply unit |
| 8297 | Bracket: suction bottle | MEQ - General | 2 | 2 | to patient supply unit |
| 8318 | Suction adapter | MEQ - General | 3 | 2 | to patient supply unit |
| 8321 | Suction bottle | MEQ - General | 3 | 2 | to patient supply unit |
| 8404 | Bracket: sharps disposal | MEQ - General | 2 | 1 | |
| 8306 | IV pole: mobile | MEQ - General | 3 | 1 | |
| 8313 | Rack: lead apron | MEQ - Imaging | 2 | 1 | |
| 21680 | Stool: adjustable, mobile | Furniture/ Fitting | 3 | 2 | |
| 8630 | Table: mayo | MEQ - Furniture | 3 | 1 | |
| 8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
| 8620 | Trolley: instrument | MEQ - Furniture | 3 | 1 | |
| 8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
| 8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 1 | |
| 8405 | Sharps disposal: wall mounted, 11L | MEQ - General | 2 | 1 | |
| 8608 | Waste bin: clinical, 120 litres | MEQ - Furniture | 3 | 1 |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 9710 | Clock: digital, electric | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9101 | Angiography table | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | part of the angiography unit |
| 8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9557 | Supply dispensing system: automated, catheter, auxiliary | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional depending on operational requirements |
| 8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8982 | Light: surgical, single, ceiling, with camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | with (optional) camera |
| 9056 | Refrigerator: drugs, under-bench, 150L | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9428 | Injector: contrast media, mobile, single head, angiography | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | or ceiling mounted injector |
| 9556 | Supply dispensing system: automated, catheter, main unit | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional depending on operational requirements |
| 30284 | Angiography: interventional cardiology, single plane, ceiling mounted | 2 | 1 | single plane or bi-plane, ceiling mounted or floor mounted depending on operational requirements |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 1006 | Voice / Data outlet: double | Communications | 3 | 1- bench; 2- patient supply unit |
| 1040 | Intercom | Communications | 1 | handsfree to control room |
| 2242 | General LED: colour corrected | Lighting | ||
| 6110 | Downlights: dimmable | Lighting | ||
| 7000 | Oxygen (O2) | Medical Gases | 2 | to patient supply unit |
| 7010 | Nitrous Oxide (N2O) | Medical Gases | 1 | to patient supply unit |
| 7020 | Medical Air (MA) | Medical Gases | 1 | to patient supply unit |
| 7040 | Suction | Medical Gases | 2 | to patient supply unit |
| 7070 | Scavenge | Medical Gases | 1 | to patient supply unit |
| 8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
| 8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
| 2579 | PO: Emergency power, single | Power | 6 | to patient supply unit |
| 2578 | PO: Emergency power, double | Power | 7 | 2 above bench; 3- wall; 1- under bench refrigerator; 1- resuscitation equipment |
| 2576 | PO: Cleaner | Power | 1 | |
| 9030 | Cardiac protected/ IPS | Power | ||
| 1005 | Voice / Data outlet: single | Communications | 3 | 1- under bench refrigerator; 2- supply automated dispensing units |
| 6076 | Special: 'X-ray In Use' lights | Lighting | 1 | |
| 2234 | Direct connection: Uninterrupted power | Power | 1 | to operating light |
| 11505 | Floor duct for power & data | Services Ducts | 1 | between equipment room, control room, and scanning room |
| 2682 | PO: Double, UPS (uninterruptible power) | Power | 2 | 2- supply dispensing units |
| 2556 | Trunking: 200mm x 70mm | Electrical Installations | 1 | between equipment room, control room, and scanning room |
| 2190 | Air pressure monitoring device | HVAC | 1 | |
| 5040 | Pressure: positive | HVAC | ||
| 2723 | PO: Cardiac Protected/IPS, single | Power | 6 | to patient supply unit |
| 2473 | Power over Ethernet (PoE) | Power | 1 | digital clock |
| 2760 | Direct connection: Voice/ Data | Communications | 1 | in-light camera (optional) |
| 2761 | Direct connection: Tool Air | Medical Gases | 1 | to patient supply unit (for brakes) |
| 2724 | Direct connection: Emergency power | Power | 1 | to patient supply unit |
| 5005 | Air conditioning: special | HVAC | HEPA filtered | |
| 12011 | Radiation shielding | Shielding | walls, floor, ceiling, doors & glazing as specificed by Radiation Consultant |