Print
Clean-up Room (Pathology)
| Room Code |
CLUP-P-I |
| Net Room Area Briefed |
12 |
| Hours of Operation |
24 Hours |
| Occupancy |
1 - 2 |
| Description / Special Requirements |
The Clean-up Room is used for rinsing and cleaning of equipment and utensils used in the Pathology Unit, and disposal of waste. |
| Amendment |
24.10.2010 First Draft
12.06.2022 RDS updated |
Fabric and outline specifications
| ID |
Fabric |
Material |
Finish |
Specification |
Selection |
Remarks |
| 3000 |
Wall finish |
Paint |
Acrylic, washable |
|
|
|
| 3795 |
Ceiling |
Plasterboard |
Prefinished |
Water resistant, drop-in tiles, 600x600mm |
|
|
| 8010 |
Door protection |
Composite |
Prefinished PVC |
Protection plate to 900mm AFFL |
|
|
| 4159 |
Cornice |
Aluminium |
Powdercoat |
Angle flush against wall, in line with ceiling grid |
|
|
| 2000 |
Skirting |
Vinyl |
Prefinished |
Floor vinyl coved, 150mmH |
|
|
| 3052 |
Wall finish |
Vinyl |
Prefinished |
Wall vinyl to 1500mm AFFL |
|
|
| 8040 |
Door protection |
Composite |
Prefinished PVC |
To door frame |
|
|
| 1020 |
Floor finish |
Vinyl, non-slip |
Safety |
Seamless, coved |
|
|
| 9127 |
Doors |
Solid Core/ Safety glass |
Paint |
1 1/2 leaf, observation panel |
|
1400mm clear opening, observation panel optional |
Fittings and Furniture (FF)
| ID |
Description |
Category |
Group |
Qty |
Selection / Remarks |
| 1010 |
Bench: stainless steel |
Metalwork |
1 |
1 |
with wet edge |
| 4410 |
Cupboard: under bench |
Furniture/ Fitting |
1 |
2 |
under SS bench, adjustable shelves |
| 4460 |
Cupboard: wall mounted |
Furniture/ Fitting |
1 |
1 |
over part SS bench, adjustable shelves |
| 6152 |
Dispenser: disposable glove |
Furniture/ Fitting |
2 |
1 |
|
| 6154 |
Dispenser: paper/ hand towel |
Furniture/ Fitting |
2 |
1 |
to basin |
| 6158 |
Dispenser: soap antiseptic |
Furniture/ Fitting |
2 |
1 |
to basin |
| 19810 |
Shelf: SS, over |
Metalwork |
1 |
1 |
over sink bench |
| 8608 |
Waste bin: clinical, 120 litres |
MEQ - Furniture |
3 |
1 |
|
| 10061 |
Waste bin: General, 20 Litres |
Furniture/ Fitting |
3 |
1 |
|
Fixtures, Equipment and associated Services (FE)
| ID |
Description |
Grp |
Qty |
Ele |
Data |
CdW |
HtW |
WmW |
Tap |
Dns |
Gas |
Selection / Remarks |
| 2800 |
Basin: handwash, Type B |
1 |
1 |
___ |
___ |
yes |
___ |
yes |
yes |
yes |
___ |
|
| 40404 |
Tapware: sensor |
1 |
1 |
yes |
___ |
yes |
yes |
yes |
___ |
___ |
___ |
straight spout |
| 40405 |
Tapware: sink mixer |
1 |
1 |
___ |
___ |
yes |
yes |
yes |
___ |
___ |
___ |
|
| 45601 |
Hose: spray |
1 |
1 |
___ |
___ |
yes |
yes |
___ |
___ |
___ |
___ |
pressure control hose spray to flushing rim sink |
| 47850 |
Sink, SS: double in bench |
1 |
1 |
___ |
___ |
yes |
opt |
opt |
yes |
yes |
___ |
|
| 49800 |
Sink: flushing rim |
1 |
1 |
___ |
___ |
yes |
opt |
___ |
___ |
yes |
___ |
in bench |
| 9348 |
Washer: laboratory, glassware, under-bench, 150L |
2 |
1 |
yes |
opt |
yes |
opt |
___ |
___ |
yes |
___ |
optional; capacity to suit service requirements |
Services
| ID |
Description |
Service Category |
Qty |
Selection / Remarks |
| 4010 |
Cold water: outlet |
Hydraulics |
1 |
to glassware washer; refer to manufacturer's requirements |
| 4033 |
Floor waste |
Hydraulics |
1 |
|
| 5000 |
Airconditioning |
HVAC |
|
|
| 5019 |
Exhaust |
HVAC |
|
efficient exhaust required |
| 2189 |
General LED |
Lighting |
|
|
| 7020 |
Medical Air (MA) |
Medical Gases |
1 |
near sinks for tube cleaning |
| 2577 |
PO: Double |
Power |
1 |
|
| 2724 |
Direct connection: Emergency power |
Power |
1 |
sensor operated tapware |
| 4045 |
Reverse osmosis (RO) water outlet |
Hydraulics |
1 |
to glassware washer; refer to manufacturer's requirements |
| 1005 |
Voice / Data outlet: single |
Communications |
1 |
to glassware washer (optional); refer to manufacturer's requirements |
| 4030 |
Drainage |
Hydraulics |
1 |
to glassware washer; refer to manufacturer's requirements |
| 4000 |
Hot water: outlet |
Hydraulics |
1 |
to glassware washer (optional); refer to manufacturer's requirements |
| 2791 |
PO: Special: 3 phase |
Power |
1 |
to glassware washer; refer to manufacturer's requirements |