A secure room also known as the Computer Server room or Technology Equipment Centre to accommodate communications racks, servers, data storage devices, interface control panels for communication systems which may include patient entertainment systems, Nurse Call and Fire/EWIS system and voice/ data backbone cabling. The room may include a small workstation area for technicians to access and maintain equipment. Room temperature should be maintained for heat generating equipment. Equipment located in this room will require uninterruptible power.
Special Design Requirements:
- Computer equipment will require protection from power surges and
spikes
- Provision of an uninterruptible power supply is required for electronic
health records servers and centralised storage to prevent data loss
- The room should be sized to accommodate the equipment required
including space for future growth
- The room should be protected from fire, potential water damage, gas
pipes and located away from sources of interference such as vibration,
electromagnetic interference, radio and radar sytems, transformers,
motors, heaters & X-ray equipment
Amendment
19.10.2015 First issue
18.05.2016 Fabric, FE and services modified
30.03.2017 Description & Services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1030
Floor finish
Vinyl
Anti-static
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
5030
Ceiling
Plasterboard
Prefinished
Drop-in tiles, 600x1200 mm
1219
Door Protection
Composite
Prefinished PVC
Kickplate, 300mm high
6025
Cornice
Aluminium
Powdercoat
shadow line
9110
Doors
Solid Core
Paint
1 1/2 leaf
1400mm/920mm clear opening; small leaf optional; lockable, card access recommended
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
optional; proprietary desk may be used
2100
Chair: ergonomic, office
Furniture/ Fitting
3
1
optional
6114
Cable tray
Furiture/fitting
1
1
for services, as required
24405
Whiteboard: magnetic
Furniture/ Fitting
2
1
900 x 900, optional
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
8760
Control panel: fire & EWIS
1
1
yes
___
___
___
___
___
___
___
as required
10890
Rack: communications
1
6
yes
yes
___
___
___
___
___
___
as required
10895
Rack: voice, IDF
1
1
yes
___
___
___
___
___
___
___
as required
11200
Computer: mainframe
3
1
yes
yes
___
___
___
___
___
___
as required
10655
Communications board
1
4
yes
___
___
___
___
___
___
___
as required
11400
Computer: PC & monitor
3
2
yes
yes
___
___
___
___
___
___
flat screen; as required
11900
Computer: server
3
1
yes
yes
___
___
___
___
___
___
as required
17100
Distribution Board
1
1
yes
___
___
___
___
___
___
___
UPS, single phase, as required
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
5
1 outlet for telephone; quantity to suit functional requirements
5000
Airconditioning
HVAC
adequate for equipment & personnel heat load; temperature alarm may be required for heat generating equipment
2189
General LED
Lighting
sensor light optional
2577
PO: Double
Power
7
quantity to suit functional requirements
9020
UPS (uninterruptible power)
Power
as required
2587
PO: Special: for equipment
Power
10
quantity to suit functional requirements; comms/ IDF racks may require 15amp power