1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code CORR-PR-I
Net Room Area Briefed 0
Hours of Operation 24 hours
Occupancy N/A
Description / Special Requirements Internal circulation Corridor in procedural areas that include HEPA filtered air such as Operating Suite, Day Surgery, Endoscopy, Medical Imaging Interventional procedures areas, Cardiac Catheter Labs, Isolation Units, Burns Unit, Oncology Units including Transplant units. Corridor widths must be sized to allow for the safe movement and passing of trolleys, beds and equipment, 2600mm to 2800mm clear width is recommended. Area (m2) is included in HPU circulation which may be esitmated as a percentage added to the Net Briefed Area or measured off a plan. 1 x GPO-Cleaner should be provided per 10 metres or as per local authority requirements. Corridor lighting, where patients are transported on trolleys, should be positioned to prevent unnecessary glare to patient eyes. Light fittings shall be recessed, flush fitting and sealed to prevent dust ingress.
Amendment 15.02.2024 First Draft

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL
3528 Wall protection Handrail at 900mm AFFL to corridors accessed by ambulant patients
9225 Doors Solid Core/ Glass Paint Double leaf, observation panel Optional; to Corridor zones; 1800mm clear opening; doors widths to ensure ease of movment of trolleys/beds; hold open devices may be applied, magnetic hold open devices to fire doors must be connected to the fire alarm system; entry doors should be lockable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6021 Cornice Tape set Paint Set between plasterboard wall and ceiling plasterboard cornice should be easy to clean and not provide dust gathering surfaces
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL where required; align heights of corner guards with other corridor elements
2530 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL, minimum
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
8040 Door protection Composite Prefinished PVC To door frame optional; to be decided at project level.

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
5830 Dispenser: antiseptic hand rub Furniture/ Fitting 2 1 Number to suit corridor layout and Infection Control policies.

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks

Services

ID Description Service Category Qty Selection / Remarks
8040 Annunciator Nurse Call 1 Ceiling mounted; number to suit corridor layout
2576 PO: Cleaner Power 1 1 every 10 metres recommended; number and location to comply with local authority requirements.
10020 Card access Security 1 To unit entry doors where required
5005 Air conditioning: special HVAC HEPA filtered air in sterile zones
2485 General LED: fully recessed Lighting sealed