Print
Cytotoxic Room
| Room Code |
CYT-I |
| Net Room Area Briefed |
8 |
| Hours of Operation |
24 Hours |
| Occupancy |
1 - 2 intermittently |
| Description / Special Requirements |
The Cytotoxic room provides for the storage and preparation of cytotoxic patient preparations including intravenous fluids and sterile items. |
| Amendment |
24.10.2010 First Draft
18.05.2023 RDS reviewed |
Fabric and outline specifications
| ID |
Fabric |
Material |
Finish |
Specification |
Selection |
Remarks |
| 1000 |
Floor finish |
Vinyl |
Standard slip resistant |
Seamless, coved |
|
|
| 2000 |
Skirting |
Vinyl |
Prefinished |
Floor vinyl coved, 150mmH |
|
|
| 5010 |
Ceiling |
Plasterboard |
Paint, washable |
Flush set, suspended |
|
|
| 8010 |
Door protection |
Composite |
Prefinished PVC |
Protection plate to 900mm AFFL |
|
|
| 9001 |
Doors |
Solid Core |
Paint |
Single leaf |
|
920mm clear opening, lockable |
| 3000 |
Wall finish |
Paint |
Acrylic, washable |
|
|
|
| 3052 |
Wall finish |
Vinyl |
Prefinished |
Wall vinyl to 1500mm AFFL |
|
tiles also acceptable |
| 2767 |
Cornice |
Plasterboard |
Paint |
Square set |
|
|
| 8040 |
Door protection |
Composite |
Prefinished PVC |
To door frame |
|
|
Fittings and Furniture (FF)
| ID |
Description |
Category |
Group |
Qty |
Selection / Remarks |
| 8629 |
Trolley: SS, multi-purpose |
MEQ - Furniture |
3 |
1 |
|
| 21680 |
Stool: adjustable, mobile |
Furniture/ Fitting |
3 |
1 |
|
| 21290 |
Cupboard: steel |
Furniture/ Fitting |
3 |
1 |
lockable |
| 9824 |
Cupboard: wall mounted, stainless steel |
Furniture/ Fitting |
1 |
1 |
|
| 1010 |
Bench: stainless steel |
Metalwork |
1 |
1 |
|
| 4420 |
Cupboard: under bench, lockable |
Furniture/ Fitting |
1 |
1 |
|
| 9199 |
Waste bin: cytotoxic, 50 litres |
MEQ - Furniture |
3 |
1 |
|
| 8407 |
Sharps disposal: cytotoxic material, 7L |
MEQ - General |
3 |
1 |
|
Fixtures, Equipment and associated Services (FE)
| ID |
Description |
Grp |
Qty |
Ele |
Data |
CdW |
HtW |
WmW |
Tap |
Dns |
Gas |
Selection / Remarks |
| 54510 |
Telephone: handset, standard |
3 |
1 |
___ |
yes |
___ |
___ |
___ |
___ |
___ |
___ |
optional, on bench |
| 8837 |
Cabinet: biological safety, cytotoxic |
2 |
1 |
yes |
___ |
___ |
___ |
___ |
___ |
___ |
___ |
biological safety cytotoxic cabinet or negative pressure cytotoxic isolator may be used depending on operational requirements |
| 9056 |
Refrigerator: drugs, under-bench, 150L |
3 |
1 |
yes |
yes |
___ |
___ |
___ |
___ |
___ |
___ |
optional, depending on operational requirements |
Services
| ID |
Description |
Service Category |
Qty |
Selection / Remarks |
| 1006 |
Voice / Data outlet: double |
Communications |
1 |
to cytotoxic cabinet (optional, refer to manufacturer's specifications) |
| 2189 |
General LED |
Lighting |
|
|
| 6055 |
Special: task light, built in |
Lighting |
|
under O/H cupboards |
| 2726 |
PO: UPS, double |
Power |
1 |
to cytotoxic cabinet |
| 5035 |
Special exhaust: hood |
HVAC |
1 |
to cytotoxic cabinet |
| 1005 |
Voice / Data outlet: single |
Communications |
1 |
to under-bench refrigerator (optional) |
| 2578 |
PO: Emergency power, double |
Power |
1 |
to under-bench refrigerator (optional) |
| 5005 |
Air conditioning: special |
HVAC |
1 |
HEPA filtered |
| 3000 |
Smoke detectors |
Fire Services |
1 |
and alarm inside room |
| 5050 |
Pressure: negative |
HVAC |
1 |
|
| 1006 |
Voice / Data outlet: double |
Communications |
1 |
to bench |
| 2578 |
PO: Emergency power, double |
Power |
1 |
to bench |