Print
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code |
CYT-I |
Net Room Area Briefed |
8 |
Hours of Operation |
24 Hours |
Occupancy |
1 - 2 intermittently |
Description / Special Requirements |
The Cytotoxic room provides for the storage and preparation of cytotoxic patient preparations including intravenous fluids and sterile items. |
Amendment |
24.10.2010 First Draft
18.05.2023 RDS reviewed |
Fabric and outline specifications
ID |
Fabric |
Material |
Finish |
Specification |
Selection |
Remarks |
1000 |
Floor finish |
Vinyl |
Standard slip resistant |
Seamless, coved |
|
|
2000 |
Skirting |
Vinyl |
Prefinished |
Floor vinyl coved, 150mmH |
|
|
5010 |
Ceiling |
Plasterboard |
Paint, washable |
Flush set, suspended |
|
|
8010 |
Door protection |
Composite |
Prefinished PVC |
Protection plate to 900mm AFFL |
|
|
9001 |
Doors |
Solid Core |
Paint |
Single leaf |
|
920mm clear opening, lockable |
3000 |
Wall finish |
Paint |
Acrylic, washable |
|
|
|
3052 |
Wall finish |
Vinyl |
Prefinished |
Wall vinyl to 1500mm AFFL |
|
tiles also acceptable |
2767 |
Cornice |
Plasterboard |
Paint |
Square set |
|
|
8040 |
Door protection |
Composite |
Prefinished PVC |
To door frame |
|
|
Fittings and Furniture (FF)
ID |
Description |
Category |
Group |
Qty |
Selection / Remarks |
8629 |
Trolley: SS, multi-purpose |
MEQ - Furniture |
3 |
1 |
|
21680 |
Stool: adjustable, mobile |
Furniture/ Fitting |
3 |
1 |
|
21290 |
Cupboard: steel |
Furniture/ Fitting |
3 |
1 |
lockable |
9824 |
Cupboard: wall mounted, stainless steel |
Furniture/ Fitting |
1 |
1 |
|
1010 |
Bench: stainless steel |
Metalwork |
1 |
1 |
|
4420 |
Cupboard: under bench, lockable |
Furniture/ Fitting |
1 |
1 |
|
9199 |
Waste bin: cytotoxic, 50 litres |
MEQ - Furniture |
3 |
1 |
|
8407 |
Sharps disposal: cytotoxic material, 7L |
MEQ - General |
3 |
1 |
|
Fixtures, Equipment and associated Services (FE)
ID |
Description |
Grp |
Qty |
Ele |
Data |
CdW |
HtW |
WmW |
Tap |
Dns |
Gas |
Selection / Remarks |
54510 |
Telephone: handset, standard |
3 |
1 |
___ |
yes |
___ |
___ |
___ |
___ |
___ |
___ |
optional, on bench |
8837 |
Cabinet: biological safety, cytotoxic |
3 |
1 |
yes |
___ |
___ |
___ |
___ |
___ |
___ |
___ |
biological safety cytotoxic cabinet or negative pressure cytotoxic isolator may be used depending on operational requirements |
9056 |
Refrigerator: drugs, under-bench, 150L |
3 |
1 |
yes |
yes |
___ |
___ |
___ |
___ |
___ |
___ |
optional, depending on operational requirements |
Services
ID |
Description |
Service Category |
Qty |
Selection / Remarks |
1006 |
Voice / Data outlet: double |
Communications |
1 |
to cytotoxic cabinet (optional, refer to manufacturer's specifications) |
2189 |
General LED |
Lighting |
|
|
6055 |
Special: task light, built in |
Lighting |
|
under O/H cupboards |
2726 |
PO: UPS, double |
Power |
1 |
to cytotoxic cabinet |
5035 |
Special exhaust: hood |
HVAC |
1 |
to cytotoxic cabinet |
1005 |
Voice / Data outlet: single |
Communications |
1 |
to under-bench refrigerator (optional) |
2578 |
PO: Emergency power, double |
Power |
1 |
to under-bench refrigerator (optional) |
5005 |
Air conditioning: special |
HVAC |
1 |
HEPA filtered |
3000 |
Smoke detectors |
Fire Services |
1 |
and alarm inside room |
5050 |
Pressure: negative |
HVAC |
1 |
|
1006 |
Voice / Data outlet: double |
Communications |
1 |
to bench |
2578 |
PO: Emergency power, double |
Power |
1 |
to bench |