Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
DTUR-12-I
Net Room Area Briefed
12
Hours of Operation
24 Hours
Occupancy
1 - 2 intermittently
Description / Special Requirements
The Dirty Utility provides for cleaning and holding of used equipment for collection and sterilisation elsewhere, disposal of clinical and other wastes and soiled linen, testing and disposing of patient specimens and decontamination and storage of patient utensils such as pans, urinals and bowls.
Acoustics: Sound attenuation level - high; Acoustic privacy required
Amendment
24.10.2010 First Draft
06.05.2011 FE updated
01.09.2022 FF, FE & Services updated
02.09.2022 Cornice updated to shadow line
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
1020
Floor finish
Vinyl, non-slip
Safety
Seamless, coved
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
9006
Doors
Solid Core/ Safety glass
Paint
Single leaf, observation panel
920mm clear opening, pull handle/push plate, closer
6025
Cornice
Aluminium
Powdercoat
shadow line
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1010
Bench: stainless steel
Metalwork
1
1
with wet edge
1455
Rack: bowl / basin
Metalwork
1
1
4494
Cupboard: urinalysis
Furniture/ Fitting
1
1
over bench, optional
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
optional
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to hand basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to hand basin
7200
Hook: equipment
Metalwork
1
2
for clean linen bags
9200
Hook: for catheter bag
Metalwork
1
2
above flushing rim sink
16500
Rack: pan & urinal
Metalwork
1
2
total of 12 pans/12 urinals
19820
Shelf: SS, under
Metalwork
1
1
@ 350mm AFFL
3960
Container: covered
Furniture/ Fitting
3
1
on / under bench; for holding items for SSU
8404
Bracket: sharps disposal
MEQ - General
2
1
8594
Linen carrier: dirty, single
MEQ - Furniture
3
3
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
8609
Waste bin: clinical, 240 litres
MEQ - Furniture
3
2
quantity may increase if macerator or bedpan/ utensil washer disinfector are not provided
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
40405
Tapware: sink mixer
1
1
___
___
yes
yes
yes
___
___
___
provide hot water
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
45601
Hose: spray
1
1
___
___
yes
yes
___
___
___
pressure control hose spray to flushing rim sink
49111
Sink: 450x350x250D
1
1
___
___
yes
opt
opt
yes
yes
___
49800
Sink: flushing rim
1
1
___
___
yes
opt
___
___
yes
___
9019
Washer disinfector: bedpan/ utensil, 100L
2
1
yes
opt
yes
yes
___
___
yes
___
optional; depends on operational policy and service requirement; with this option macerator is not required
30112
Macerator
1
1
optional; depends on operational policy and service requirement; with this option bedpan/ utensil washer disinfector is not required
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
5019
Exhaust
HVAC
2189
General LED
Lighting
2577
PO: Double
Power
1
2724
Direct connection: Emergency power
Power
1
for sensor operated tapware
4045
Reverse osmosis (RO) water outlet
Hydraulics
1
or softened water for bedpan/ utensil washer disinfector (if selected); depends on operational policy and service requirement
5015
Ventilation
HVAC
4010
Cold water: outlet
Hydraulics
1
for macerator or bedpan/ utensil washer disinfector; depends on operational policy and service requirement
4030
Drainage
Hydraulics
1
for macerator or bedpan/ utensil washer disinfector; depends on operational policy and service requirement
2582
PO: Single
Power
1
for macerator (if selected); depends on operational policy and service requirement
2791
PO: Special: 3 phase
Power
1
for bedpan/ utensil washer disinfector (if selected); depends on operational policy and service requirement