1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code DTUR-12-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy 1 - 2 intermittently
Description / Special Requirements The Dirty Utility provides for cleaning and holding of used equipment for collection and sterilisation elsewhere, disposal of clinical and other wastes and soiled linen, testing and disposing of patient specimens and decontamination and storage of patient utensils such as pans, urinals and bowls. Acoustics: Sound attenuation level - high; Acoustic privacy required
Amendment 24.10.2010 First Draft 06.05.2011 FE updated 01.09.2022 FF, FE & Services updated 02.09.2022 Cornice updated to shadow line

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3795 Ceiling Plasterboard Prefinished Water resistant, drop-in tiles, 600x600mm
1020 Floor finish Vinyl, non-slip Safety Seamless, coved
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 920mm clear opening, pull handle/push plate, closer
6025 Cornice Aluminium Powdercoat shadow line

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1010 Bench: stainless steel Metalwork 1 1 with wet edge
1455 Rack: bowl / basin Metalwork 1 1
4494 Cupboard: urinalysis Furniture/ Fitting 1 1 over bench, optional
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1 optional
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to hand basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to hand basin
7200 Hook: equipment Metalwork 1 2 for clean linen bags
9200 Hook: for catheter bag Metalwork 1 2 above flushing rim sink
16500 Rack: pan & urinal Metalwork 1 2 total of 12 pans/12 urinals
19820 Shelf: SS, under Metalwork 1 1 @ 350mm AFFL
3960 Container: covered Furniture/ Fitting 3 1 on / under bench; for holding items for SSU
8404 Bracket: sharps disposal MEQ - General 2 1
8594 Linen carrier: dirty, single MEQ - Furniture 3 3
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
8609 Waste bin: clinical, 240 litres MEQ - Furniture 3 2 quantity may increase if macerator or bedpan/ utensil washer disinfector are not provided
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___ provide hot water
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
45601 Hose: spray 1 1 ___ ___ yes yes ___ ___ ___ pressure control hose spray to flushing rim sink
49111 Sink: 450x350x250D 1 1 ___ ___ yes opt opt yes yes ___
49800 Sink: flushing rim 1 1 ___ ___ yes opt ___ ___ yes ___
9019 Washer disinfector: bedpan/ utensil, 100L 2 1 yes opt yes yes ___ ___ yes ___ optional; depends on operational policy and service requirement; with this option macerator is not required
30112 Macerator 1 1 optional; depends on operational policy and service requirement; with this option bedpan/ utensil washer disinfector is not required

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5019 Exhaust HVAC
2189 General LED Lighting
2577 PO: Double Power 1
2724 Direct connection: Emergency power Power 1 for sensor operated tapware
4045 Reverse osmosis (RO) water outlet Hydraulics 1 or softened water for bedpan/ utensil washer disinfector (if selected); depends on operational policy and service requirement
5015 Ventilation HVAC
4010 Cold water: outlet Hydraulics 1 for macerator or bedpan/ utensil washer disinfector; depends on operational policy and service requirement
4030 Drainage Hydraulics 1 for macerator or bedpan/ utensil washer disinfector; depends on operational policy and service requirement
2582 PO: Single Power 1 for macerator (if selected); depends on operational policy and service requirement
2791 PO: Special: 3 phase Power 1 for bedpan/ utensil washer disinfector (if selected); depends on operational policy and service requirement