Print Download PDF Version
Dirty Utility, 14m2
Room Code
DTUR-14-I
Net Room Area Briefed
14
Hours of Operation
24 Hours
Occupancy
1 - 2 intermittently
Description / Special Requirements
The Dirty Utility provides for cleaning and holding of used equipment for collection and sterilisation elsewhere, disposal of clinical and other wastes and soiled linen, testing and disposing of patient specimens and decontamination and storage of patient utensils such as pans, urinals and bowls.
Acoustics: Sound attenuation level - high; Acoustic privacy required
Amendment
24.10.2010 First Draft
02.05.2011 FF & FE remarks updated
28.05.2014 General amendments to FF
04.07.2016 Document amended to match RLS.
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
1020
Floor finish
Vinyl, non-slip
Safety
Seamless, coved
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
3000
Wall finish
Paint
Acrylic, washable
9006
Doors
Solid Core/ Safety glass
Paint
Single leaf, observation panel
920mm clear opening, pull handle/push plate, closer
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1010
Bench: stainless steel
Metalwork
1
1
with wet edge
1455
Rack: bowl / basin
Metalwork
1
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
optional
3960
Container: covered
Furniture/ Fitting
3
1
on / under bench; for holding items for SSU
4494
Cupboard: urinalysis
Furniture/ Fitting
1
1
over bench
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to hand basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to hand basin
7200
Hook: equipment
Metalwork
1
2
for clean linen bags
8404
Bracket: sharps disposal
MEQ - General
2
1
wall mounted
8594
Linen carrier: dirty, single
MEQ - Furniture
3
3
9200
Hook: for catheter bag
Metalwork
1
2
above flushing rim sink
16500
Rack: pan & urinal
Metalwork
1
2
total of 12 pans/12 urinals
19820
Shelf: SS, under
Metalwork
1
1
@ 350mm AFFL
8609
Waste bin: clinical, 240 litres
MEQ - Furniture
3
2
quantity may increase if macerator or bedpan/ utensil washer disinfector are not provided
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
9019
Washer disinfector: bedpan/ utensil, 100L
2
1
yes
opt
yes
yes
___
___
yes
___
optional; depends on operational policy and service requirement; with this option macerator is not required
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
40405
Tapware: sink mixer
1
1
___
___
yes
yes
yes
___
___
___
provide hot water
45601
Hose: spray
1
1
___
___
yes
yes
___
___
___
___
pressure control hose spray to flushing rim sink
49111
Sink: 450x350x250D
1
1
___
___
yes
opt
opt
yes
yes
___
49800
Sink: flushing rim
1
1
___
___
yes
opt
___
___
yes
___
30112
Macerator
2
1
optional; depends on operational policy and service requirement; with this option bedpan/ utensil washer disinfector is not required
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
5015
Ventilation
HVAC
5019
Exhaust
HVAC
2189
General LED
Lighting
2577
PO: Double
Power
1
2724
Direct connection: Emergency power
Power
1
for sensor operated tapware
4045
Reverse osmosis (RO) water outlet
Hydraulics
1
or softened water for bedpan/ utensil washer disinfector (if selected); depends on operational policy and service requirement
4010
Cold water: outlet
Hydraulics
1
for macerator or bedpan/ utensil washer disinfector; depends on operational policy and service requirement
4030
Drainage
Hydraulics
1
for macerator or bedpan/ utensil washer disinfector; depends on operational policy and service requirement
2582
PO: Single
Power
1
for macerator (if selected); depends on operational policy and service requirement
2791
PO: Special: 3 phase
Power
1
for bedpan/ utensil washer disinfector (if selected); depends on operational policy and service requirement