The Electronics Laboratory provides a secure workshop area for use by electricians to handle, test, repair, calibrate or service items of electrical equipment used in the hospital. This includes specialist medical equipment serviced by Biomedical Technicians. The workshop may be located in close proximity to the Biomedical Workshop.
Amendment
24.10.2010 First Draft
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, tiles or other smooth impervious finish also acceptable
3000
Wall finish
Paint
Acrylic, washable
9127
Doors
Solid Core/ Safety glass
Paint
1 1/2 leaf, observation panel
1400mm clear opening; lockable
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900mm AFFL
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
900AFFL
1950
Chair: ergonomic, high
Furniture/ Fitting
3
2
4420
Cupboard: under bench, lockable
Furniture/ Fitting
1
1
under part bench
4470
Cupboard: wall mounted, lockable
Furniture/ Fitting
1
1
over bench
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54510
Telephone: handset, standard
3
2
___
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
2724
Direct connection: Emergency power
Power
1
sensor operated tapware
2587
PO: Special: for equipment
Power
1
20A, for equipment testing
2587
PO: Special: for equipment
Power
1
3 phase for equipment testing
9040
Body protected
Power
2577
PO: Double
Power
9