Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
ENS-BA-I
Net Room Area Briefed
7
Hours of Operation
24 Hours
Occupancy
1 patient; 1-2 staff assisting
Description / Special Requirements
The Bariatric Ensuite is designed to meet the needs of bariatric (obsese or morbidly obese) patients allowing the patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance.
The Ensuite - Bariatric is associated with the 1 Bed Room - Bariatric: the additional area and layout will facilitate two assisting nurses and a shower commode with bariatric capacity. The Ensuite and Bedroom should be planned as an integral suite to optimise the use of a ceiling mounted hoist between the two rooms.
Acoustics: sound attenuation level - High. Acoustic privacy required.
Additional Design Requirements:
- The shower floor must not have a raised hob
- The entrance is to be flush with the adjoining floor
- The door is to be fitted with escape hardware.
Body protected electrical area.
Amendment
02.07.2015 First Draft
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
8040
Door protection
Composite
Prefinished PVC
To door frame
9110
Doors
Solid Core
Paint
1 1/2 leaf
1200mm clear outward opening, privacy latch, emergency release
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
or other coved skirting to match floor
3035
Wall finish
Vinyl
Prefinished
Wall vinyl full height
other smooth impervious finish also acceptable
1020
Floor finish
Vinyl, non-slip
Safety
Seamless, coved
other non-slip impervious floor finish suitable for barefeet also acceptable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
3400
Coathook
Metalwork
1
2
4800
Curtain track: shower
Metalwork
1
1
5300
Curtain: shower
Furniture/ Fitting
3
1
5673
Chair: shower, bariatric
Furniture/ Fitting
3
1
or commode chair, bariatric capacity
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
2
2
1 - to basin; 1 - to shower (optional)
6160
Dispenser: toilet paper
Furniture/ Fitting
2
1
locate on drop down rail
8309
Oxygen flowmeter
MEQ - General
3
1
optional
8400
Grab rail: WC
Metalwork
1
2
both sides of toilet, fixings to support bariatric capacity
8450
Grab rail: Shower
Metalwork
1
1
combined with hand held shower; fixings to support bariatric capacity
8500
Grab rail: WC, hinged
Metalwork
1
2
drop down rails both sides of toilet; 1 side with toilet paper dispenser; 1 side with patient to staff call; fixings to support bariatric capacity
10800
Hook: for IV flasks
Metalwork
1
2
13700
Mirror
Metalwork
1
1
over basin
19100
Waste bin: sanitary
Furniture/ Fitting
3
1
optional
20603
Soap/ shampoo holder: recessed
Furniture/ Fitting
1
1
23700
Towel rail
Metalwork
1
1
with grab rail strength and fixings to support bariatric capacity
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3003
Bidet handset
1
1
___
___
___
___
yes
yes
___
___
near toilet; optional
5603
Basin: ensuite
1
1
___
___
yes
___
yes
yes
yes
___
or floor basin with a separate shelf; fixings to support bariatric capacity
8978
Patient lift: overhead track, bariatric, w sling
1
1
yes
___
___
___
___
___
___
___
optional; track from bedroom; provide track only if track continuous from bedroom
5602
Toilet suite: bariatric
1
1
___
___
yes
___
___
yes
yes
___
concealed cistern optional
40402
Tapware: basin mixer
1
1
___
___
yes
yes
yes
___
___
___
fixture mounted
40406
Tapware: shower mixer
1
1
___
___
yes
yes
yes
___
___
___
47400
Shower: hand-held
1
1
___
___
yes
___
yes
yes
yes
___
fixings to support bariatric capacity
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
8080
Emergency call
Nurse Call
1
+ indicator button & light
5019
Exhaust
HVAC
for heat/ steam
2189
General LED
Lighting
9040
Body protected
Power
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8000
Patient to Staff call
Nurse Call
2
+ indicator button & light; 1 - shower & 1 - toilet (may be located on drop down rail beside toilet)
7000
Oxygen (O2)
Medical Gases
1
optional
5015
Ventilation
HVAC
2587
PO: Special: for equipment
Power
1
for hair dryer & shaver use only; to comply with relevant electric safety guidelines