1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code ENS-BA-I
Net Room Area Briefed 7
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff assisting
Description / Special Requirements The Bariatric Ensuite is designed to meet the needs of bariatric (obsese or morbidly obese) patients allowing the patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance. The Ensuite - Bariatric is associated with the 1 Bed Room - Bariatric: the additional area and layout will facilitate two assisting nurses and a shower commode with bariatric capacity. The Ensuite and Bedroom should be planned as an integral suite to optimise the use of a ceiling mounted hoist between the two rooms. Acoustics: sound attenuation level - High. Acoustic privacy required. Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining floor - The door is to be fitted with escape hardware. Body protected electrical area.
Amendment 02.07.2015 First Draft 03.09.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
8040 Door protection Composite Prefinished PVC To door frame
9110 Doors Solid Core Paint 1 1/2 leaf 1200mm clear outward opening, privacy latch, emergency release
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
3795 Ceiling Plasterboard Prefinished Water resistant, drop-in tiles, 600x600mm
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH or other coved skirting to match floor
3035 Wall finish Vinyl Prefinished Wall vinyl full height other smooth impervious finish also acceptable
1020 Floor finish Vinyl, non-slip Safety Seamless, coved other non-slip impervious floor finish suitable for barefeet also acceptable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
3400 Coathook Metalwork 1 2
4800 Curtain track: shower Metalwork 1 1
5300 Curtain: shower Furniture/ Fitting 3 1
5673 Chair: shower, bariatric Furniture/ Fitting 3 1 or commode chair, bariatric capacity
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 2 1 - to basin; 1 - to shower (optional)
6160 Dispenser: toilet paper Furniture/ Fitting 2 1 locate on drop down rail
8309 Oxygen flowmeter MEQ - General 3 1 optional
8400 Grab rail: WC Metalwork 1 2 both sides of toilet, fixings to support bariatric capacity
8450 Grab rail: Shower Metalwork 1 1 combined with hand held shower; fixings to support bariatric capacity
8500 Grab rail: WC, hinged Metalwork 1 2 drop down rails both sides of toilet; 1 side with toilet paper dispenser; 1 side with patient to staff call; fixings to support bariatric capacity
10800 Hook: for IV flasks Metalwork 1 2
13700 Mirror Metalwork 1 1 over basin
19100 Waste bin: sanitary Furniture/ Fitting 3 1 optional
20603 Soap/ shampoo holder: recessed Furniture/ Fitting 1 1
23700 Towel rail Metalwork 1 1 with grab rail strength and fixings to support bariatric capacity
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3003 Bidet handset 1 1 ___ ___ ___ ___ yes yes ___ ___ near toilet; optional
5603 Basin: ensuite 1 1 ___ ___ yes ___ yes yes yes ___ or floor basin with a separate shelf; fixings to support bariatric capacity
8978 Patient lift: overhead track, bariatric, w sling 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional; track from bedroom; provide track only if track continuous from bedroom
5602 Toilet suite: bariatric 1 1 ___ ___ yes ___ ___ yes yes ___ concealed cistern optional
40402 Tapware: basin mixer 1 1 ___ ___ yes yes yes ___ ___ ___ fixture mounted
40406 Tapware: shower mixer 1 1 ___ ___ yes yes yes ___ ___ ___
47400 Shower: hand-held 1 1 ___ ___ yes ___ yes yes yes ___ fixings to support bariatric capacity

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
8080 Emergency call Nurse Call 1 + indicator button & light
5019 Exhaust HVAC for heat/ steam
2189 General LED Lighting
9040 Body protected Power
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8000 Patient to Staff call Nurse Call 2 + indicator button & light; 1 - shower & 1 - toilet (may be located on drop down rail beside toilet)
7000 Oxygen (O2) Medical Gases 1 optional
5015 Ventilation HVAC
2587 PO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply with relevant electric safety guidelines