Print Download PDF Version
Ensuite - Birthing Room
Room Code
ENS-BR-I-A
Net Room Area Briefed
10
Hours of Operation
24 Hours
Occupancy
1 patient; 1-2 staff assisting
Description / Special Requirements
The Birthing Room Ensuite is for the Birthing Room patient to wash, shower, use the toilet, and bath as desired for pain relief, either independently or with assistance. The area and layout must accommodate an assisting nurse. The Ensuite will include a shower, handbasin, toilet and an island bath. The island bath will include steps and a seating platform at the bath edge.
Acoustics: Sound attenuation level - High. Acoustic privacy required.
Body Protected Electrical Area
Additional Design Requirements:
- The shower floor must not have a raised hob
- The entrance is to be flush with the adjoining flooring
- The door is to be fitted with escape hardware
Amendment
24.10.10, - First Draft
05.05.11, - Services modified
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5023
Ceiling
Plasterboard
Prefinished
Water resistant, drop in tiles, 600x1200
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
9001
Doors
Solid Core
Paint
Single leaf
920 clear outward opening, privacy latch, emergency release
7001
Windows
optional, obscure glass
1175
Floor finish
Tiles
Non-slip
Ceramic
vinyl also acceptable
2145
Skirting
Tiles
To match floor
Coved
or coved tiled skirting
3080
Wall finish
Tiles
Glazed
Full height
vinyl also acceptable
6025
Cornice
Aluminium
Powdercoat
shadow line
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
2300
Chair: shower
Furniture/ Fitting
3
1
3400
Coathook
Metalwork
1
2
1 @ 1200 AFFL for wheelchair users
4800
Curtain track: shower
Metalwork
1
1
5300
Curtain: shower
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
6156
Dispenser: soap
Furniture/ Fitting
2
1
6160
Dispenser: toilet paper
Furniture/ Fitting
1
1
8400
Grab rail: WC
Metalwork
1
2
1 behind toilet, 1 to side
8430
Grab rail: Bath
Metalwork
1
1
8450
Grab rail: Shower
Metalwork
1
1
8500
Grab rail: WC, hinged
Metalwork
1
1
optional, drop down rail
9200
Hook: for catheter bag
Metalwork
1
3
10800
Hook: for IV flasks
Metalwork
1
3
13700
Mirror
Metalwork
1
1
over basin
20650
Soap/ shampoo holder
Furniture/ Fitting
1
1
23700
Towel rail
Metalwork
1
1
with grab rail strength and fixings
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to hand basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
refer to BHWS-B (sim)
3003
Bidet handset
1
1
___
___
___
___
yes
yes
___
___
near toilet
3200
Bath: patient
1
1
___
___
yes
___
yes
yes
yes
___
island, with steps & seating platform
47400
Shower: hand-held
1
1
___
___
yes
___
yes
yes
yes
___
47400
Shower: hand-held
1
1
___
___
yes
___
yes
yes
yes
___
low level over bath
55605
Toilet suite: patient
1
1
___
___
yes
___
___
yes
yes
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
2
5000
Airconditioning
HVAC
5019
Exhaust
HVAC
for steam/ heat
6001
General: colour corrected
Lighting
7000
Oxygen (O2)
Medical Gases
1
Optional
7010
Nitrous Oxide (N2O)
Medical Gases
1
Optional
7070
Scavenge
Medical Gases
1
Optional
8000
Patient/ Staff call
Nurse Call
3
+ indicator button & light
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2577
PO: Double
Power
1
locate near door outside room
9040
Body protected
Power
2587
PO: Special: for equipment
Power
1
for hair dryer & shaver use only; to comply with relevant electric safety guidelines