Room Code ENS-BR-I-B
Net Room Area Briefed 5
Hours of Operation 24 Hours
Occupancy 1 patient; 1 staff assisting
Description / Special Requirements An Ensuite, Birthing Room is for the patient to wash, shower and use the toilet, either independently or with assistance. The area and layout must accommodate an assisting nurse, and wheelchair access. The Ensuite will have direct access from the Birthing Room. Acoustics: Sound attenuation level - High. Acoustic privacy required. Body Protected Electrical Area Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining flooring - The door is to be fitted with escape hardware
Amendment 24.10.10, - First Draft 05.05.11, - Services modified

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
5023 Ceiling Plasterboard Prefinished Water resistant, drop in tiles, 600x1200
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
9001 Doors Solid Core Paint Single leaf 920 clear outward opening, privacy latch, emergency release
8040 Door protection Composite Prefinished PVC To door frame
1175 Floor finish Tiles Non-slip Ceramic vinyl also acceptable
2145 Skirting Tiles To match floor Coved or coved floor vinyl skirting
3080 Wall finish Tiles Glazed Full height to wet areas; vinyl also acceptable
3000 Wall finish Paint Acrylic, washable
6025 Cornice Aluminium Powdercoat shadow line

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
2300 Chair: shower Furniture/ Fitting 3 1 optional
3400 Coathook Metalwork 1 2 1 @ 1200 AFFL for wheelchair users
4800 Curtain track: shower Metalwork 1 1
5300 Curtain: shower Furniture/ Fitting 3 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1
6156 Dispenser: soap Furniture/ Fitting 2 1
6160 Dispenser: toilet paper Furniture/ Fitting 1 1
8400 Grab rail: WC Metalwork 1 2 1 behind toilet, 1 to side
8450 Grab rail: Shower Metalwork 1 1
8500 Grab rail: WC, hinged Metalwork 1 1 optional
9200 Hook: for catheter bag Metalwork 1 2
10800 Hook: for IV flasks Metalwork 1 2
13700 Mirror Metalwork 1 1 over basin
19100 Waste bin: sanitary Furniture/ Fitting 3 1
20650 Soap/ shampoo holder Furniture/ Fitting 1 1
23700 Towel rail Metalwork 1 1 with grab rail strength and fixings
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to hand basin

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2850 Basin: handwash, Type C 1 1 ___ ___ yes ___ yes yes yes ___ refer to BHWS-C (sim)
3003 Bidet handset 1 1 ___ ___ ___ ___ yes yes ___ ___ near toilet
47400 Shower: hand-held 1 1 ___ ___ yes ___ yes yes yes ___
55605 Toilet suite: patient 1 1 ___ ___ yes ___ ___ yes yes ___

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC
5019 Exhaust HVAC for steam/ heat
2189 General LED Lighting
8000 Patient/ Staff call Nurse Call 2 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2577 PO: Double Power 1 locate near door outside room
9040 Body protected Power
2587 PO: Special: for equipment Power 1 for hair dryer & shaver use only; to comply with relevant electric safety guidelines