The Ensuite - Mental Health will provide a shower, toilet and handbasin for use by mental health patients. The Ensuite will be lockable and Master Keyed from the outside with a privacy latch on the inside.
The Ensuite - Mental Health may vary in configuration to suit different room types including:
- ENS-MH-A Inboard Ensuite with direct access, for 1 or 2 Bed Rooms
- ENS-MH-B Inboard Ensuite with access from corridor, for 1 or 2 Bed
Rooms
- ENS-MH-D Inboard Ensuite for 2 Bed Room, with direct access
Acoustics: Sound attenuation level high; Acoustic privacy required
Body Protected electrical area
Additional Design Considerations:
- Two floor wastes will be required
- Fittings are to have a breaking strain of not more than 15 kg
- Grab rails, shower and door furniture must not provide points for ligature
- Cisterns should be concealed
- All glazing in the room including mirror to be unbreakable
- An 'observation bay' which may include thermostatic mixing & shut off
valves and RCD is optional
Amendment
24.10.10, - First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
5021
Ceiling
Plasterboard
Paint, washable
Water resistant, flush set, suspended
6010
Cornice
Plasterboard
Paint
90mm to match ceiling finish
8040
Door protection
Composite
Prefinished PVC
To door frame
9001
Doors
Solid Core
Paint
Single leaf
920 clear outward opening, privacy latch, key lockable as required by safety risk assessment