1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code ENS-MH-I
Net Room Area Briefed 5
Hours of Operation 24 Hours
Occupancy 1 patient; 1 staff assisting as required
Description / Special Requirements The Ensuite - Mental Health will provide a shower, toilet and handbasin for use by mental health patients. The Ensuite will be lockable and Master Keyed from the outside with a privacy latch on the inside. The Ensuite - Mental Health may vary in configuration to suit different room types including: - ENS-MH-A Inboard Ensuite with direct access, for 1 or 2 Bed Rooms - ENS-MH-B Inboard Ensuite with access from corridor, for 1 or 2 Bed Rooms - ENS-MH-D Inboard Ensuite for 2 Bed Room, with direct access Acoustics: Sound attenuation level high; Acoustic privacy required Body Protected electrical area Additional Design Considerations: - Two floor wastes will be required - Fittings are to have a breaking strain of not more than 15 kg - Grab rails, shower and door furniture must not provide points for ligature - Cisterns should be concealed - All glazing in the room including mirror to be unbreakable - An 'observation bay' which may include thermostatic mixing & shut off valves and RCD is optional
Amendment 24.10.2010 First Draft 03.09.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
5021 Ceiling Plasterboard Paint, washable Water resistant, flush set, suspended
2767 Cornice Plasterboard Paint Square set
9001 Doors Solid Core Paint Single leaf 920 clear outward opening, privacy latch, key lockable as required by safety risk assessment
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH or other coved skirting to match floor
3035 Wall finish Vinyl Prefinished Wall vinyl full height other smooth impervious finish also acceptable
1020 Floor finish Vinyl, non-slip Safety Seamless, coved other non-slip impervious floor finish suitable for barefeet also acceptable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1329 Coathook: collapsible Metalwork 1 2
4800 Curtain track: shower Metalwork 1 1 plastic, ceiling mounted/ recessed
5300 Curtain: shower Furniture/ Fitting 3 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 no sharp cutting edges
6156 Dispenser: soap Furniture/ Fitting 2 1 optional
6160 Dispenser: toilet paper Furniture/ Fitting 2 1
8400 Grab rail: WC Metalwork 1 1 vertical with infill, ligature resistant
8450 Grab rail: Shower Metalwork 1 1 vertical with infill, ligature resistant
13730 Mirror: acrylic Metalwork 1 1 optional; may also use safety glass mirror
19910 Shelf: vanity Furniture/ Fitting 1 1 recessed
20603 Soap/ shampoo holder: recessed Furniture/ Fitting 1 1 recessed
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
1142 Toilet suite: concealed cistern 1 1 ___ ___ yes ___ ___ yes yes ___ bidet to be anti-ligature with concealed piping if provided
10334 Basin: handwash, anti-ligature 1 1 ___ ___ yes ___ yes yes yes ___
10333 Tapware: basin, anti-ligature 1 1 ___ ___ yes yes yes ___ ___ ___
10332 Tapware: shower, anti-ligature 1 1 ___ ___ yes yes yes ___ ___ ___
10331 Shower: anti-ligature 1 1 ___ ___ yes ___ yes yes yes ___

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 2
5019 Exhaust HVAC for heat/ steam
8000 Patient to Staff call Nurse Call 2 + indicator button & light
2738 General LED: vandal proof Lighting
5015 Ventilation HVAC