Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
ENS-SVIP-I
Net Room Area Briefed
20
Hours of Operation
24 Hours
Occupancy
1 patient; 1 staff assisting
Description / Special Requirements
An Ensuite - Super VIP is for a patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance. The area and layout must accommodate an assisting nurse, patient lifter and assisted wheelchair access. The Ensuite - Super VIP may include a bath. An island bath will require an increase in the room area.
Acoustics: Sound attenuation level - High. Acoustic privacy required.
Body Protected Electrical Area
Additional Design Requirements:
- The shower floor must not have a raised hob
- The entrance is to be flush with the adjoining flooring
- The door is to be fitted with escape hardware
Amendment
24.10.10, - First Draft
26.05.11, - Fabric, FF & Services modified
08.04.13, - Fabric modified;
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5021
Ceiling
Plasterboard
Paint, washable
Water resistant, flush set, suspended
1250
Floor finish
Tiles
Polished
Stone/ Marble 15mm
2147
Skirting
Tiles
To match floor
1324
Wall finish
Tiles
Polished
Stone/ Marble, full height
9001
Doors
Solid Core
Paint
Single leaf
920 clear outward opening, privacy latch, emergency release
6025
Cornice
Aluminium
Powdercoat
shadow line
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
1
optional
350
Artwork
Furniture/ Fitting
3
2
optional
530
Basin vanity top
Furniture/ Fitting
1
1
stone/ granite
1000
Bench seat
Furniture/ Fitting
1
3
stone; 2 to bath area; 1 in shower
1465
Bracket: suction bottle
Furniture/ Fitting
2
1
optional
3400
Coathook
Metalwork
1
2
1 @ 1200 AFFL for wheelchair users
4330
Cupboard: wardrobe
Furniture/ Fitting
1
1
4391
Cupboard: special
Furniture/ Fitting
1
1
to conceal medical gases; optional
6156
Dispenser: soap
Furniture/ Fitting
2
1
optional
6160
Dispenser: toilet paper
Furniture/ Fitting
2
1
8400
Grab rail: WC
Metalwork
1
2
1 behind toilet, 1 to side; inclusion depends on operational policy
8430
Grab rail: Bath
Metalwork
1
1
inclusion depends on operational policy
8450
Grab rail: Shower
Metalwork
1
1
inclusion depends on operational policy
8500
Grab rail: WC, hinged
Metalwork
1
1
optional; inclusion depends on operational policy
9200
Hook: for catheter bag
Metalwork
1
2
inclusion depends on operational policy
10800
Hook: for IV flasks
Metalwork
1
2
inclusion depends on operational policy
13700
Mirror
Metalwork
1
1
over basin
16250
Oxygen flowmeter
Furniture/ Fitting
3
1
optional
20055
Partitions: shower
Furniture/ Fitting
1
1
20650
Soap/ shampoo holder
Furniture/ Fitting
1
1
21950
Suction adapter
Furniture/ Fitting
3
1
optional
22000
Suction bottle
Furniture/ Fitting
3
1
optional
23700
Towel rail
Metalwork
1
2
with grabrail strength & fixings
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to hand basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
recessed in wall; provide service panel behind TV
3120
Basin: vanity
1
1
___
___
yes
___
yes
yes
yes
___
3600
Bath: spa
1
1
___
___
yes
___
yes
yes
yes
___
or adjustable height bath / island bath
47400
Shower: hand-held
1
1
___
___
yes
___
yes
yes
yes
___
47500
Shower: fixed rose
1
1
___
___
yes
___
yes
yes
yes
___
rain shower head
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
wall telephone
55605
Toilet suite: patient
1
1
___
___
yes
___
___
yes
yes
___
55607
Toilet suite: bidet
1
1
___
___
yes
___
___
yes
yes
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1005
Voice / Data outlet: single
Communications
1
to telephone
1090
TV: MATV
Communications
1
4035
Floor trough
Hydraulics
3
with SS grille in shower
5000
Airconditioning
HVAC
5019
Exhaust
HVAC
for steam/ heat
6000
General fluorescent
Lighting
6125
Vanity (concealed)
Lighting
7000
Oxygen (O2)
Medical Gases
1
optional
7040
Suction
Medical Gases
1
optional
8000
Patient/ Staff call
Nurse Call
3
+ indicator button & light
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
9001
GPO: Double
Power
1
locate near door in vestibule
9040
Body protected
Power
9060
GPO: Special: for equipment
Power
1
for hair dryer & shaver use only; to comply with relevant electric safety guidelines
9060
GPO: Special: for equipment
Power
1
waterproof for TV
45570471
Special: decorative
Lighting