1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
ECL-SP-I
Net Room Area Briefed
8
Hours of Operation
24 Hours
Occupancy
1 - 2
Description / Special Requirements
The Clean-up/ Sub Pathology room is used for rinsing and cleaning of equipment used in the Unit, and for satellite pathology equipment such as a blood gas analyser for urgent blood testing. The room may be located in a Critical Care Unit.
Amendment
24.10.10, - First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1020
Floor finish
Vinyl, non-slip
Safety
Seamless, coved
3000
Wall finish
Paint
Acrylic, washable
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
5023
Ceiling
Plasterboard
Prefinished
Water resistant, drop in tiles, 600x1200
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
9004
Doors
Solid Core/ Glass
Paint
Single leaf, observation panel
920mm clear opening
6025
Cornice
Aluminium
Powdercoat
shadow line
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
8040
Door protection
Composite
Prefinished PVC
To door frame
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1010
Bench: stainless steel
Metalwork
1
1
with wet edge, inset sinks
4410
Cupboard: under bench
Furniture/ Fitting
1
1
under SS bench
4460
Cupboard: wall mounted
Furniture/ Fitting
1
1
over part SS bench
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to basin
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
Refer to BHWS-B (sim)
4650
blood gas analyser
3
1
yes
___
___
___
___
___
yes
___
optional
47850
Sink, SS: double in bench
1
1
___
___
yes
opt
opt
yes
yes
___
hot water
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
5000
Airconditioning
HVAC
6000
General fluorescent
Lighting
6055
Special: task light, built in
Lighting
1
to underside of O/H cupboards
9001
GPO: Double
Power
2
9060
GPO: Special: for equipment
Power
1
blood gas analyser, as required