Equipment Clean-up, 10m2

Room Code ECL-10-I
Net Room Area Briefed 10
Hours of Operation 24 Hours
Occupancy 1 - 2
Description / Special Requirements The Equipment Clean-Up Room is used for cleaning and maintaining of equipment used in the Unit. Storage may be required for holding cleaned equipment and spares. Equipment may also be recharged in this room. Natural light is desirable.
Amendment 24.10.2010 First Draft 06.05.2011 FF and FE updated 31.08.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
5021 Ceiling Plasterboard Paint, washable Water resistant, flush set, suspended
1020 Floor finish Vinyl, non-slip Safety Seamless, coved
2767 Cornice Plasterboard Paint Square set
3000 Wall finish Paint Acrylic, washable
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 1100mm clear opening, lockable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1010 Bench: stainless steel Metalwork 1 1 with wet edge, inset sinks
4360 Cupboard: door ht adj. shelves Furniture/ Fitting 1 1 optional
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
19820 Shelf: SS, under Metalwork 1 1 under bench
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 over bench
8629 Trolley: SS, multi-purpose MEQ - Furniture 3 2 optional
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 2

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
4045 Tapware: elbow mixer 1 2 ___ ___ yes yes yes ___ ___ ___ provide hot water, to sinks
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
45601 Hose: spray 1 1 ___ ___ yes yes ___ ___ ___ optional
49005 Sink: 500x450x300D 1 2 ___ ___ yes opt opt yes yes ___

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5015 Ventilation HVAC
5019 Exhaust HVAC
2189 General LED Lighting
2577 PO: Double Power 2
2724 Direct connection: Emergency power Power 1 for sensor operated tapware