1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code ECL-SP-I
Net Room Area Briefed 8
Hours of Operation 24 Hours
Occupancy 1 - 2
Description / Special Requirements The Clean-up/ Sub Pathology room is used for rinsing and cleaning of equipment used in the Unit, and for satellite pathology equipment such as a blood gas analyser for urgent blood testing. The room may be located in a Critical Care Unit.
Amendment 24.10.2010 First Draft 03.09.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
3795 Ceiling Plasterboard Prefinished Water resistant, drop-in tiles, 600x600mm
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
8040 Door protection Composite Prefinished PVC To door frame
1020 Floor finish Vinyl, non-slip Safety Seamless, coved
3000 Wall finish Paint Acrylic, washable
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 920mm clear opening

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1010 Bench: stainless steel Metalwork 1 1 with wet edge, inset sinks
4410 Cupboard: under bench Furniture/ Fitting 1 1 under SS bench
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over part SS bench
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___ provide hot water; wrist operated lever taps
47850 Sink, SS: double in bench 1 1 ___ ___ yes opt opt yes yes ___
9017 Analyser: blood gas, point-of-care, 30 samples/hr 3 1 opt opt ___ ___ ___ ___ ___ ___ optional, depending on operational requirements

Services

ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC
2189 General LED Lighting
6055 Special: task light, built in Lighting under O/H cupboards
2577 PO: Double Power 2
2724 Direct connection: Emergency power Power 1 sensor operated tapware
2578 PO: Emergency power, double Power 1 to laboratory equipment, as required
1006 Voice / Data outlet: double Communications 1 to laboratory equipment, as required