Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
ECL-SP-I
Net Room Area Briefed
8
Hours of Operation
24 Hours
Occupancy
1 - 2
Description / Special Requirements
The Clean-up/ Sub Pathology room is used for rinsing and cleaning of equipment used in the Unit, and for satellite pathology equipment such as a blood gas analyser for urgent blood testing. The room may be located in a Critical Care Unit.
Amendment
24.10.2010 First Draft
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
8040
Door protection
Composite
Prefinished PVC
To door frame
1020
Floor finish
Vinyl, non-slip
Safety
Seamless, coved
3000
Wall finish
Paint
Acrylic, washable
9006
Doors
Solid Core/ Safety glass
Paint
Single leaf, observation panel
920mm clear opening
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1010
Bench: stainless steel
Metalwork
1
1
with wet edge, inset sinks
4410
Cupboard: under bench
Furniture/ Fitting
1
1
under SS bench
4460
Cupboard: wall mounted
Furniture/ Fitting
1
1
over part SS bench
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to basin
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
40405
Tapware: sink mixer
1
1
___
___
yes
yes
yes
___
___
___
provide hot water; wrist operated lever taps
47850
Sink, SS: double in bench
1
1
___
___
yes
opt
opt
yes
yes
___
9017
Analyser: blood gas, point-of-care, 30 samples/hr
3
1
opt
opt
___
___
___
___
___
___
optional, depending on operational requirements
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
5000
Airconditioning
HVAC
2189
General LED
Lighting
6055
Special: task light, built in
Lighting
under O/H cupboards
2577
PO: Double
Power
2
2724
Direct connection: Emergency power
Power
1
sensor operated tapware
2578
PO: Emergency power, double
Power
1
to laboratory equipment, as required
1006
Voice / Data outlet: double
Communications
1
to laboratory equipment, as required