to basin; hot water water is blended to warm water
62400
IMG: control booth
1
1
yes
yes
___
___
___
___
___
___
optional, if control area walls are not created
Services
ID
Description
Service Category
Qty
Selection / Remarks
1040
Intercom
Communications
1
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
6110
Downlights: dimmable
Lighting
7000
Oxygen (O2)
Medical Gases
1
patient services panel
7040
Suction
Medical Gases
1
patient services panel
8080
Emergency call
Nurse Call
1
patient services panel
2582
PO: Single
Power
2
patient services panel
2579
PO: Emergency power, single
Power
2
patient services panel
9040
Body protected
Power
12011
Radiation shielding
Shielding
to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
1006
Voice / Data outlet: double
Communications
6
1-bench; 1- patient services panel; 1- lithotripsy equipment within the exam room; 2- lithotripsy control workstation (control booth); 1- wall (can be used for ultrasound unit)
2233
Direct connection: Emergency power
Power
1
to sensor tap
8010
Staff/ Nurse assist call
Nurse Call
1
patient services panel
6076
Special: 'X-ray In Use' lights
Lighting
1
2546
Cabinet: generator
Power
1
2577
PO: Double
Power
3
2 - walls; 1 - bench
7020
Medical Air (MA)
Medical Gases
1
patient services panel
9029
Electrical Isolator: 3PH+N
Power
1
1- x-ray generator cabinet
2726
PO: UPS, double
Power
5
2- lithotripsy control workstation (control booth); 1- ultrasound unit (on walls inside the exam room); 1- lithotripsy unit; 1- patient table