Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
FEED-I
Net Room Area Briefed
7
Hours of Operation
24 Hours
Occupancy
Up to 3
Description / Special Requirements
The Feeding Room provides an area for mothers to feed babies with staff assistance as required or to express breast milk. The Feeding Room will be located adjacent to the General Nursery with ready access to the Formula Room.The room will be used for feeding of neonates with or without nursing staff assistance, and expressing of breast milk in privacy. Room privacy including privacy latches and screening will be required and a handbasin will be located in close proximity.
Acoustics: Sound attenuation medium, acoustic protection required
Body Protected electrical area
Amendment
24.10.2010 - First draft
02.05.2011 - Fabric updated
14.01.2016 - Description & Services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
3000
Wall finish
Paint
Acrylic, washable
5060
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x1200
9004
Doors
Solid Core/ Glass
Paint
Single leaf, observation panel
To Formula Room; 920mm clear opening, privacy latch, lockable
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
6025
Cornice
Aluminium
Powdercoat
shadow line
9001
Doors
Solid Core
Paint
Single leaf
Entry from Corridor; 920mm clear opening; privacy latch, lockable
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
8040
Door protection
Composite
Prefinished PVC
To door frame
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
350
Artwork
Furniture/ Fitting
3
1
optional
2000
Chair: lounge
Furniture/ Fitting
3
2
2655
Chair: visitor
Furniture/ Fitting
3
1
3400
Coathook
Metalwork
1
1
4700
Curtain track: privacy screen
Metalwork
1
1
to entry door
5250
Curtain: privacy screen
Furniture/ Fitting
3
1
to entry door
22800
Table: low
Furniture/ Fitting
3
2
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
1 outlet for telephone if provided
5000
Airconditioning
HVAC
6000
General fluorescent
Lighting
6110
Downlights: dimmable
Lighting
9000
GPO: Single
Power
4
9040
Body protected
Power
8080
Emergency call
Nurse Call
1
+ indicator button & light
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light