1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code FST-2-I
Net Room Area Briefed 2
Hours of Operation 24 Hours
Occupancy 1 - 2
Description / Special Requirements The Flash Steriliser is a bay for washing and rapid sterilising of instruments that are dropped in Operating Room procedures. The Flash Steriliser Bay will be located with ready access to the Operating Rooms.
Amendment 24.10.2010 First Draft 02.05.2011 FE remarks updated 13.03.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1020 Floor finish Vinyl, non-slip Safety Seamless, coved
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL tiles also acceptable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
2767 Cornice Plasterboard Paint Square set
3000 Wall finish Paint Acrylic, washable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1010 Bench: stainless steel Metalwork 1 1 with wet edge
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to sink
6156 Dispenser: soap Furniture/ Fitting 2 1 to sink
19820 Shelf: SS, under Metalwork 1 1 under bench
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 over bench

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___ provide hot water
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___
9559 Steriliser: steam, benchtop, 20L 2 1 yes opt yes ___ ___ ___ yes ___ capacity & quantity depend on operational requirements

Services

ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
2189 General LED Lighting
4045 Reverse osmosis (RO) water outlet Hydraulics 1 to steam steriliser (optional, refer to manufacturer's specifications)
4030 Drainage Hydraulics 1 to steam steriliser (optional, refer to manufacturer's specifications)
1005 Voice / Data outlet: single Communications 1 to steam steriliser (optional, refer to manufacturer's specifications)
2578 PO: Emergency power, double Power 1 to steam steriliser