Fluoroscopy Room is a room for undertaking radiographic procedures involving contrast media. Patient Change, Toilets and Shower should be lcoated in close proximity. The room may include a preparation area with sink.
Additional Design Requirements:
- Radiation sheilding to walls and glazing as advised by Radiation
Consultant
- Unistrut type ceiling may be required, depending on equipment to be
installed
- Cable ducting between the X-ray table, vertical bucky and control area
may be required, depending on equipment type and layout
- 'X-ray in Use' warning lights will be required outside each entry door
Body Protected electrical area
Amendment
24.10.2010 First Draft
21.04.2011 Outline specifications, FF and Services modified
21.06.2019 Room name and room code updated
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
8040
Door protection
Composite
Prefinished PVC
To door frame
9130
Doors
Solid Core
Paint
1 1/2 leaf, with lead shielding
Patient entry/exit 1400mm clear opening
7025
Observation
Lead glass
Clear
Internal window
to control booth
9001
Doors
Solid Core
Paint
Single leaf
to Patient Change/ Toilet and Staff Entry
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
3000
Wall finish
Paint
Acrylic, washable
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin & sink, other smooth impervious finish also acceptable
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
at 3000mm AFFL
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1010
Bench: stainless steel
Metalwork
1
1
with wet edge
1090
Bench: laminate, free standing
Furniture/ Fitting
3
1
workstation
2150
Chair: patient
Furniture/ Fitting
3
1
4410
Cupboard: under bench
Furniture/ Fitting
1
1
adjustable shelf
4460
Cupboard: wall mounted
Furniture/ Fitting
1
1
over bench
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
1
to services panel
8309
Oxygen flowmeter
MEQ - General
3
1
to services panel
8321
Suction bottle
MEQ - General
3
1
8313
Rack: lead apron
MEQ - Imaging
1
1
24450
Workstation: laminated
Furniture/ Fitting
3
1
pull-out shelf for keyboard
8297
Bracket: suction bottle
MEQ - General
2
1
8318
Suction adapter
MEQ - General
3
1
2100
Chair: ergonomic, office
Furniture/ Fitting
3
1
8402
Footstool: 2-step
MEQ - Furniture
3
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
11400
Computer: PC & monitor
3
1
yes
yes
___
___
___
___
___
___
flat screen
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
40405
Tapware: sink mixer
1
1
___
___
yes
yes
yes
___
___
___
warm water, to sink
47800
Sink, SS: single in bench
1
1
___
___
yes
opt
opt
yes
yes
___
9092
Control console
2
1
yes
yes
___
___
___
___
___
___
inside booth; may be located in separate Control Room
9095
X-ray unit: chest
2
1
yes
yes
___
___
___
___
___
___
optional
9099
X-ray table
2
1
yes
___
___
___
___
___
___
___
9643
X-ray unit: radiography/ fluoroscopy, digital
2
1
yes
yes
___
___
___
___
___
___
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
wall mounted
62400
IMG: control booth
2
1
yes
yes
___
___
___
___
___
___
with lead glazing; not required if separate Control Room provided
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
3
1- control console; 1- computer; 1- bench
1040
Intercom
Communications
1
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
6055
Special: task light, built in
Lighting
under O/H cupboards
6005
Dimmable
Lighting
7000
Oxygen (O2)
Medical Gases
1
patient services panel
7020
Medical Air (MA)
Medical Gases
1
patient services panel
7040
Suction
Medical Gases
1
patient services panel
8010
Staff/ Nurse assist call
Nurse Call
1
8080
Emergency call
Nurse Call
1
patient services panel
2582
PO: Single
Power
2
patient services panel
2579
PO: Emergency power, single
Power
2
patient services panel
9040
Body protected
Power
11000
Wall panel
Services Panels
1
flush mounted
12011
Radiation shielding
Shielding
to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
2724
Direct connection: Emergency power
Power
1
sensor operated tapware
6826
Trunking: 150mm x 70mm
Electrical Installations
1
between x-ray fluoroscopy equipment, chest bucky, patient table and control console
6076
Special: 'X-ray In Use' lights
Lighting
1
6827
Cabinet: generator
Power
1
to power fluoroscopy system and chest bucky, supplied by imaging vendor
2791
PO: Special: 3 phase
Power
1
to fluoroscopy system equipment generator
2726
PO: UPS, double
Power
4
2- control console; 2- computer
2578
PO: Emergency power, double
Power
4
1- bench; 3- walls
11505
Floor duct for power & data
Services Ducts
1
between x-ray fluoroscopy equipment, chest bucky, patient table and control console