Frozen section is part of Pathology in a OR, wherein it allows pathologists to rapidly analyze and diagnose tissue samples while the patient is still in the operating room
Amendment
26.02.2024 First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
antimicrobial; refer to K&A ID Drawings for specs
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
6132
Skirting
Vinyl
Prefinished
Floor vinyl coved, 100mmH
1703
Doors
Solid Core/ Glass
Laminate
Single leaf, observation panel
920mm clear opening, Lockable
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
8040
Door protection
Composite
Prefinished PVC
To door frame
6025
Cornice
Aluminium
Powdercoat
shadow line
3060
Wall finish
Vinyl
Prefinished
Splashback
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
4335
Cupboard: double door lockable
Furniture/ Fitting
1
1
4410
Cupboard: under bench
Furniture/ Fitting
1
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
6156
Dispenser: soap
Furniture/ Fitting
2
1
6157
Dispenser: medicated hand gel
Furniture/ Fitting
2
1
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
8607
Waste bin: clinical, 50 litres
MEQ - Furniture
3
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
9334
Microtome: cryostat, freestanding
3
1
yes
___
___
___
___
___
___
___
9294
Microscope: upright
3
1
yes
___
___
___
___
___
___
___
8832
Cabinet: biological safety, Class II, Type A2
2
1
yes
___
___
___
___
___
___
9059
Refrigerator: laboratory, single door, 700L
3
1
yes
yes
___
___
___
___
___
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1005
Voice / Data outlet: single
Communications
1
to laboratory refrigerator
2578
PO: Emergency power, double
Power
3
1- laboratory refrigerator; 2- bench
5000
Airconditioning
HVAC
1
2578
PO: Emergency power, double
Power
1
1 for cryostat microtome
1006
Voice / Data outlet: double
Communications
1
to bench
5035
Special exhaust: hood
HVAC
1
to biosafety cabinet
2726
PO: UPS, double
Power
1
to biosafety cabinet
1006
Voice / Data outlet: double
Communications
1
to biosafety cabinet (optional, refer to manufacturer's specifications and operational requirements)