Gamma Camera is a room for undertaking imaging procedures on patients using radiopharmaceutical preparations. The room requires direct access to the Control Room/ area and close access to waiting areas.
Body Protected electrical area
Additional Design Requirements:
- Radiation sheilding to walls and glazing as advised by Radiation
Consultant
- Adequate airconditioning and ventilation is required for equipment
functioning
- Cable ducting between the table and control area may be required
- Structural assessment required; average weight of camera has a point
load of approximately 2 tonnes over 1m x 2m square area
- Equipment and services required are to be installed to manufacturer's
specifications
Amendment
24.10.2010 First Draft
02.05.2011 FF updated
17.01.2017 Description, Fabric, FF, FE & Services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900 AFFL
4030
Wall protection
Composite
Prefinished PVC
Corner guards to 900 AFFL
5030
Ceiling
Plasterboard
Prefinished
Drop-in tiles, 600x1200 mm
flush set plasterboard ceiling also acceptable
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
9130
Doors
Solid Core
Paint
1 1/2 leaf, with lead shielding
1400mm clear opening
6025
Cornice
Aluminium
Powdercoat
shadow line
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, tiles or other smooth impervious finish also acceptable
3000
Wall finish
Paint
Acrylic, washable
8040
Door protection
Composite
Prefinished PVC
To door frame
7025
Observation
Lead glass
Clear
Internal window
to Control area
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
1
to services panel
1050
Bench: laminate
Furniture/ Fitting
1
1
with inset sink, optional
1465
Bracket: suction bottle
Furniture/ Fitting
2
1
wall mounted
1650
Chair: client
Furniture/ Fitting
3
1
2100
Chair: ergonomic, office
Furniture/ Fitting
3
1
to control area
3350
Clock: battery operated
Furniture/ Fitting
3
1
3600
Cart: collimator
Furniture/ Fitting
3
1
4360
Cupboard: door ht adj. shelves
Furniture/ Fitting
1
1
optional
4410
Cupboard: under bench
Furniture/ Fitting
1
1
optional
4470
Cupboard: wall mounted, lockable
Furniture/ Fitting
1
1
over bench; adjustable shelves; optional
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
2
to basin & sink
6156
Dispenser: soap
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
16250
Oxygen flowmeter
Furniture/ Fitting
3
1
to services panel
21950
Suction adapter
Furniture/ Fitting
3
1
to services panel
22000
Suction bottle
Furniture/ Fitting
3
1
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
taps: sensor outlet; elbow action lever taps also acceptable
22200
IMG: Gamma camera imaging unit
1
1
yes
yes
___
___
___
___
___
___
including computer modules
47800
Sink, SS: single in bench
1
1
___
___
yes
opt
opt
yes
yes
___