Gown-up

Room Code GW-UP-I
Net Room Area Briefed 6
Hours of Operation 24 Hours
Occupancy 1 - 2
Description / Special Requirements Gown-up is a room with dual doors for visitors or staff to put on personal protective equipment (PPE) before entering a Unit. Room should be located on the perimeter of the unit with one direction flow. Door entering the Unit is controlled by staff from the Staff Station or Reception of the Unit. An intercom system with a camera and monitor connecting to the Staff Station or Reception will be desirable.
Amendment 14.01.2019 First Draft 03.09.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin; other smooth impervious finish also acceptable
3000 Wall finish Paint Acrylic, washable
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 920mm clear opening; electronic locking controlled by Staff Station/ Reception
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
2767 Cornice Plasterboard Paint Square set

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
3400 Coathook Metalwork 1 2 on wall
5897 Cabinet: PPE Furniture/ Fitting 1 1 for gowns, overshoes, masks etc
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
24102 Waste bin: general Furniture/ Fitting 3 1 to basin; foot pedal operated
8607 Waste bin: clinical, 50 litres MEQ - Furniture 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout

Services

ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
2576 PO: Cleaner Power 1
2724 Direct connection: Emergency power Power 1 sensor operated tapware
2467 Downlights: LED Lighting
2275 Video intercom Communications 1 optional but recommended
2760 Direct connection: Voice/ Data Communications 1 if video Intercom provided
9050 Direct connection Power 1 if video Intercom provided