Gown-up is a room with dual doors for visitors or staff to put on personal protective equipment (PPE) before entering a Unit. Room should be located on the perimeter of the unit with one direction flow. Door entering the Unit is controlled by staff from the Staff Station or Reception of the Unit. An intercom system with a camera and monitor connecting to the Staff Station or Reception will be desirable.
Amendment
14.01.2019 First Draft
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin; other smooth impervious finish also acceptable
3000
Wall finish
Paint
Acrylic, washable
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
9006
Doors
Solid Core/ Safety glass
Paint
Single leaf, observation panel
920mm clear opening; electronic locking controlled by Staff Station/ Reception