Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
GYAH-60-I
Net Room Area Briefed
60
Hours of Operation
8am to 6pm daily
Occupancy
Up to 6 patients/ hour; up to 4 staff
Description / Special Requirements
The Gymnasium provides for patient evaluation, rehabilitation exercise activities, therapy and ambulation training. An external outlook is desirable. The Gym area will require access for wheelchairs and staff handwashing facilties. The equipment to be used in this area will be dependent on the funtion of the gym and the Operational Policy.
Acoustics: Acoustic privacy required.
Body protected electrical area
Special Design Requirements
- Floors, walls and ceilings must be structurally able to support exercise
and weight training equipment that may be required in the gym
Amendment
24.10.2010 First Draft
02.05.2011 Fabric, FF & Services updated
02.03.2017 Description, Fabric updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
cushioned vinyl optional
3000
Wall finish
Paint
Acrylic, washable
7001
Windows
desirable
8040
Door protection
Composite
Prefinished PVC
To door frame
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin & sink, tiles or other smooth impervious finish also acceptable
6025
Cornice
Aluminium
Powdercoat
shadow line
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
5060
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x1200 mm
flush set plasterboard acoustic ceiling also acceptable
9125
Doors
Solid Core/ Glass
Paint
1 1/2 leaf, observation panel
Patient Entry/Exit; 1400 mm clear opening, lockable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
optional
1250
Blind: Venetian
Metalwork
3
1
1 to each external/ internal window, if provided
1650
Chair: client
Furniture/ Fitting
3
4
3350
Clock: battery operated
Furniture/ Fitting
3
1
4410
Cupboard: under bench
Furniture/ Fitting
1
1
optional
4430
Cupboard: drawer unit
Furniture/ Fitting
1
1
under bench, optional
4460
Cupboard: wall mounted
Furniture/ Fitting
1
1
over bench; adjustable shelves; optional
4600
Curtain track: bed screen
Metalwork
1
2
to plinth spaces
5000
Curtain: bed screen
Furniture/ Fitting
3
2
to plinth spaces
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
2
to basin & sink
6156
Dispenser: soap
Furniture/ Fitting
2
2
to basin & sink
7520
Exercise bicycle
Furniture/ Fitting
3
2
optional
7530
Exercise stairs
Furniture/ Fitting
3
1
optional
8866
Plinth: single
Furniture/ Fitting
3
1
8867
Plinth: double
Furniture/ Fitting
3
1
13645
Steel mesh: framed, ceiling mount
Metalwork
1
2
to plinths, optional
13646
Steel mesh: framed, wall mount
Metalwork
1
2
to plinths, optional
13800
Mirror: full length
Metalwork
1
1
to one wall
16780
Parallel bars
Furniture/ Fitting
3
1
1 set; removable
18170
Pulley weights: wall mounted
Furniture/ Fitting
3
1
optional
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
taps: sensor outlet; elbow action lever taps also acceptable
47890
Sink & drainer: single, 930mmL
1
1
___
___
yes
opt
opt
yes
yes
___
sink optional, provide hot water
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
wall phone
Services
ID
Description
Service Category
Qty
Selection / Remarks
1000
Telephone: PABX
Communications
1
to wall phone
1006
Voice / Data outlet: double
Communications
3
1 to each plinth space; 1 to bench
5000
Airconditioning
HVAC
6000
General fluorescent
Lighting
8000
Patient/ Staff call
Nurse Call
2
1 to each plinth space; + indicator button & light
8005
Patient call handset
Nurse Call
2
1 to each plinth space; call button on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
9001
GPO: Double
Power
10
quantity will be determined by equipment to be used and Operational Policy
9015
GPO: Cleaner
Power
1
9040
Body protected
Power