Room Code | HTLB-PET-I |
Net Room Area Briefed | 12 |
Hours of Operation | 8am to 6pm, daily |
Occupancy | 1 |
Description / Special Requirements | The Hot Laboratory is an area for storage and preparation of radiopharmaceuticals for use in imaging procedures. The area will include a preparation bench, cupboards and sink with touch free taps. Space will be required for dose calibration, record keeping and quality assurance activities. If pre-prepared materials are used, storage and calculation areas may be considerably smaller than for on-site preparation. Radionuclide storage areas and waste storage within the space may require sheilding, including benches and cupboards. The Hot Laboratory will be located with ready access to Nuclear Imaging Rooms and dosing areas. Additional Design Considerations - Radiation shielding to be advised by Radiation Consultant - The floors and walls should be constructed of a material that is easily decontaminated, with no gaps or crevices - Vents and traps for radioactive gases should be provided if such are used |
Amendment | 24.10.2010 First Draft 02.05.2011 FE remarks updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin, other smooth impervious finish also acceptable | |
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | as required; other heights also acceptable as per project standardisation | |
2767 | Cornice | Plasterboard | Paint | Square set | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
1709 | Doors | Solid Core | Laminate | Single leaf, with lead shielding | 920mm clear opening, lockable |
ID | Description | Category | Group | Qty | Selection / Remarks |
1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | with wet edge and inset sink |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | laminate, adjustable shelves |
4460 | Cupboard: wall mounted | Furniture/ Fitting | 1 | 1 | over bench, adjustable shelves |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to sink |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to sink |
24102 | Waste bin: general | Furniture/ Fitting | 3 | 1 | small, in radiation sheilded cupboard |
8667 | Safe: storage, lead lined | MEQ - Nuclear Medicine | 3 | 1 | optional, lead lined |
8611 | Waste bin: radioactive, 20 litres | MEQ - Nuclear Medicine | 3 | 1 | |
8663 | Sharps disposal: lead lined | MEQ - Nuclear Medicine | 3 | 1 | may be deleted if supplised as part of PET unit dose storage cabinet |
9065 | Kit: emergency, radioactivity spillage, on trolley | MEQ - Nuclear Medicine | 3 | 1 | |
8672 | Cabinet: storage, lead lined, PET unit dose | MEQ - Nuclear Medicine | 3 | 1 | |
8671 | Cabinet: storage, lead lined, w shelves & drawers | MEQ - Nuclear Medicine | 3 | 1 | |
9064 | Dosimeter: pocket | MEQ - Nuclear Medicine | 3 | 1 | Qty depends on operational requirements |
9062 | Survey meter: contamination, G-M detector | MEQ - Nuclear Medicine | 3 | 1 | |
8664 | Survey meter: scintillation | MEQ - Nuclear Medicine | 3 | 1 | |
8957 | Trolley: radiopharmaceuticals, shielded | MEQ - Nuclear Medicine | 3 | 1 | shielding thickness depends on operational requirements |
10156 | Allowance: hot laboratory, PET | MEQ - Nuclear Medicine | 3 | 1 | to include syringe shields, vial shields, syringe carriers, tongs... etc, details and quantity depend on operational requirements |
10158 | Allowance: QC & calibration sources | MEQ - Nuclear Medicine | 3 | 1 | as required, depending on operational requirements |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
47800 | Sink, SS: single in bench | 1 | 1 | ___ | ___ | yes | opt | opt | yes | yes | ___ | confirm sink dimensions ; provide hot water |
9166 | Radiation area monitor: digital, wall mounted | 2 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | one inside the room and one outside the room |
7300 | Camera: CCTV security | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9132 | Cabinet: storage, lead lined, sink and waste | 3 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
9140 | Well counter: wipe testing, lead lined | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
9142 | Dose calibrator: multipurpose | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | may be deleted if supplised as part of PET unit dose storage cabinet |
10046 | Laminar flow hood: radioisotope, 1500mm | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional, may replace the PET unit dose storage cabinet depending on operational requirements |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | straight spout |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 5 | 4- bench (as required); 1- wall |
5000 | Airconditioning | HVAC | ||
2189 | General LED | Lighting | ||
6055 | Special: task light, built in | Lighting | under O/H cupboards | |
2724 | Direct connection: Emergency power | Power | 2 | 1- sensor operated tapware; 1- CCTV camera |
2579 | PO: Emergency power, single | Power | 2 | to radiation area monitors |
2578 | PO: Emergency power, double | Power | 6 | 5- bench (as required); 1- wall |
10020 | Card access | Security | 1 | |
12011 | Radiation shielding | Shielding | 1 | |
5019 | Exhaust | HVAC | 1 | to radioisotope hood (optional, refer to manufacturer's specifications) |
7022 | Compressed air | Medical Gases | 1 | to radioisotope hood (optional or gas, refer to manufacturer's specifications) |
4010 | Cold water: outlet | Hydraulics | 1 | to sink and waste storage cabinet (refer to manufacturer's specifications) |
4030 | Drainage | Hydraulics | 1 | to sink and waste storage cabinet (refer to manufacturer's specifications) |
4000 | Hot water: outlet | Hydraulics | 1 | to sink and waste storage cabinet (refer to manufacturer's specifications) |
2579 | PO: Emergency power, single | Power | 3 | to radioisotope hood (optional, from top, refer to manufacturer's specifications) |