1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code HTLB-PET-I
Net Room Area Briefed 12
Hours of Operation 8am to 6pm, daily
Occupancy 1
Description / Special Requirements The Hot Laboratory is an area for storage and preparation of radiopharmaceuticals for use in imaging procedures. The area will include a preparation bench, cupboards and sink with touch free taps. Space will be required for dose calibration, record keeping and quality assurance activities. If pre-prepared materials are used, storage and calculation areas may be considerably smaller than for on-site preparation. Radionuclide storage areas and waste storage within the space may require sheilding, including benches and cupboards. The Hot Laboratory will be located with ready access to Nuclear Imaging Rooms and dosing areas. Additional Design Considerations - Radiation shielding to be advised by Radiation Consultant - The floors and walls should be constructed of a material that is easily decontaminated, with no gaps or crevices - Vents and traps for radioactive gases should be provided if such are used
Amendment 24.10.2010 First Draft 02.05.2011 FE remarks updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required; other heights also acceptable as per project standardisation
2767 Cornice Plasterboard Paint Square set
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
1709 Doors Solid Core Laminate Single leaf, with lead shielding 920mm clear opening, lockable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1030 Bench: resinate Furniture/ Fitting 1 1 with wet edge and inset sink
4410 Cupboard: under bench Furniture/ Fitting 1 1 laminate, adjustable shelves
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over bench, adjustable shelves
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to sink
6156 Dispenser: soap Furniture/ Fitting 2 1 to sink
24102 Waste bin: general Furniture/ Fitting 3 1 small, in radiation sheilded cupboard
8667 Safe: storage, lead lined MEQ - Nuclear Medicine 3 1 optional, lead lined
8611 Waste bin: radioactive, 20 litres MEQ - Nuclear Medicine 3 1
8663 Sharps disposal: lead lined MEQ - Nuclear Medicine 3 1 may be deleted if supplised as part of PET unit dose storage cabinet
9065 Kit: emergency, radioactivity spillage, on trolley MEQ - Nuclear Medicine 3 1
8672 Cabinet: storage, lead lined, PET unit dose MEQ - Nuclear Medicine 3 1
8671 Cabinet: storage, lead lined, w shelves & drawers MEQ - Nuclear Medicine 3 1
9064 Dosimeter: pocket MEQ - Nuclear Medicine 3 1 Qty depends on operational requirements
9062 Survey meter: contamination, G-M detector MEQ - Nuclear Medicine 3 1
8664 Survey meter: scintillation MEQ - Nuclear Medicine 3 1
8957 Trolley: radiopharmaceuticals, shielded MEQ - Nuclear Medicine 3 1 shielding thickness depends on operational requirements
10156 Allowance: hot laboratory, PET MEQ - Nuclear Medicine 3 1 to include syringe shields, vial shields, syringe carriers, tongs... etc, details and quantity depend on operational requirements
10158 Allowance: QC & calibration sources MEQ - Nuclear Medicine 3 1 as required, depending on operational requirements

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___ confirm sink dimensions ; provide hot water
9166 Radiation area monitor: digital, wall mounted 2 2 yes opt ___ ___ ___ ___ ___ ___ one inside the room and one outside the room
7300 Camera: CCTV security 1 1 yes ___ ___ ___ ___ ___ ___ ___
9132 Cabinet: storage, lead lined, sink and waste 3 1 ___ ___ yes ___ yes yes yes ___
9140 Well counter: wipe testing, lead lined 3 1 yes opt ___ ___ ___ ___ ___ ___
9142 Dose calibrator: multipurpose 3 1 yes opt ___ ___ ___ ___ ___ ___ may be deleted if supplised as part of PET unit dose storage cabinet
10046 Laminar flow hood: radioisotope, 1500mm 2 1 yes ___ ___ ___ ___ ___ ___ ___ optional, may replace the PET unit dose storage cabinet depending on operational requirements
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 5 4- bench (as required); 1- wall
5000 Airconditioning HVAC
2189 General LED Lighting
6055 Special: task light, built in Lighting under O/H cupboards
2724 Direct connection: Emergency power Power 2 1- sensor operated tapware; 1- CCTV camera
2579 PO: Emergency power, single Power 2 to radiation area monitors
2578 PO: Emergency power, double Power 6 5- bench (as required); 1- wall
10020 Card access Security 1
12011 Radiation shielding Shielding 1
5019 Exhaust HVAC 1 to radioisotope hood (optional, refer to manufacturer's specifications)
7022 Compressed air Medical Gases 1 to radioisotope hood (optional or gas, refer to manufacturer's specifications)
4010 Cold water: outlet Hydraulics 1 to sink and waste storage cabinet (refer to manufacturer's specifications)
4030 Drainage Hydraulics 1 to sink and waste storage cabinet (refer to manufacturer's specifications)
4000 Hot water: outlet Hydraulics 1 to sink and waste storage cabinet (refer to manufacturer's specifications)
2579 PO: Emergency power, single Power 3 to radioisotope hood (optional, from top, refer to manufacturer's specifications)