1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code HBOT-2-I
Net Room Area Briefed 60
Hours of Operation 24 Hours
Occupancy 2 patients; 1 - 2 staff
Description / Special Requirements The Hyperbaric Oxygen Therapy (HBOT) Room provides a controlled environment, privacy and facilities for carrying out treatments in two individual rigid pressure vessels or chambers which are able to deliver 100% oxygen. HBOT may be used for treatment of air embolism, decompression sickness, gas gangrene and carbon monoxide poisoning. The room will be directly connected to a toilet/s with changing facilities including lockers. Special Design Consideration - Floor finish must be anti-static - Sealed ceiling must be provided - tile ceiling is to be avoided. - No fluorescent lighting to be provided in room. - Fire suppression system to be installed as per manufacturer's requirements - Separate air vents required for each HBOT chamber for maintenance of Infection Control - Sensor taps, if installed, should be connected to essential power supply. Acoustics: Sound attenuation level - high; Acoustic privacy is required. Body Protected electrical area
Amendment 05.05.2020 First Draft 03.09.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
8040 Door protection Composite Prefinished PVC To door frame
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 1400mm clear opening; lockable; observation panel optional
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH or other skirting to match floor finish
3000 Wall finish Paint Acrylic, washable
2767 Cornice Plasterboard Paint Square set
1030 Floor finish Vinyl Anti-static Seamless, coved other anti-static flooring also acceptable
3038 Wall finish Vinyl Prefinished Wall vinyl to 900mm AFFL
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
7001 Windows optional; if provided, position must not expose the chamber to direct sunlight
4030 Wall protection Composite Prefinished PVC Corner guards to 900mm AFFL as required; other heights also acceptable as per project standardisation

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1
1252 Blind: Venetian integral Furniture/ Fitting 1 1 to external window if provided
2909 Bracket: television Furniture/ Fitting 2 2 may be ceiling, wall or HBOT chamber mounted
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
4360 Cupboard: door ht adj. shelves Furniture/ Fitting 1 1
4410 Cupboard: under bench Furniture/ Fitting 1 1 adjustable shelf, optional
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 1 over bench, adjustable shelf, optional
4600 Curtain track: bed screen Metalwork 1 2 recessed ceiling mounted track also acceptable
5000 Curtain: bed screen Furniture/ Fitting 3 2
5920 Desk: computer Furniture/ Fitting 3 1 between 2 HBOT chambers
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 for multiple sizes
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 1 to services panel
8297 Bracket: suction bottle MEQ - General 2 1
8309 Oxygen flowmeter MEQ - General 3 1 to services panel
8318 Suction adapter MEQ - General 3 1 to services panel
8404 Bracket: sharps disposal MEQ - General 2 1
8594 Linen carrier: dirty, single MEQ - Furniture 3 1
8321 Suction bottle MEQ - General 3 1 to services panel
8607 Waste bin: clinical, 50 litres MEQ - Furniture 3 1
8613 Trolley: clean linen, medium MEQ - Furniture 3 1
8626 Trolley: dressing, 2 drawer MEQ - Furniture 3 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 2 yes ___ ___ ___ ___ ___ ___ ___
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
30109 Hyperbaric chamber: monoplace 3 2 includes associated patient trolleys, accessories & connections
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ optional, wall mounted or on bench

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1- desk; 1- bench
5000 Airconditioning HVAC as per HBOT chamber manufacturer's requirements
2242 General LED: colour corrected Lighting
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2577 PO: Double Power 4 2- desk; 2- bench
2576 PO: Cleaner Power 1
9040 Body protected Power
2724 Direct connection: Emergency power Power 1 sensor operated tapware
2587 PO: Special: for equipment Power 2 for HBOT chamber as per manufacturer's specification
5015 Ventilation HVAC as per HBOT chamber manufacturer's requirements
2559 IPTV Communications 2
2582 PO: Single Power 2 TV
7050 Gas Alarm Panel Medical Gases 1 to HBOT chambers as per manufacturer's specification
4015 Chilled water supply Hydraulics 2 if water cooled model is selected, as per HBOT chamber manufacturer's requirements
8000 Patient to Staff call Nurse Call 2 to HBOT chambers as per manufacturer's specification
1040 Intercom Communications 2 to HBOT chambers as per manufacturer's specification
2153 Audio input Communications 2 to HBOT chambers as per manufacturer's specification
7020 Medical Air (MA) Medical Gases 2 @ 70psi pressure connection to HBOT chamber as per manufacturer's specification
7020 Medical Air (MA) Medical Gases 1 to patient services panel
7000 Oxygen (O2) Medical Gases 1 to patient services panel
11000 Wall panel Services Panels 1
7000 Oxygen (O2) Medical Gases 2 high pressure connection to HBOT chamber as per manufacturer's specification
2579 PO: Emergency power, single Power 2 to patient services panel
2582 PO: Single Power 2 to patient services panel
6055 Special: task light, built in Lighting 1 under O/H cupboards
7040 Suction Medical Gases 1 to patient services panel
1006 Voice / Data outlet: double Communications 2 as per HBOT chamber manufacturer's requirements (optional)