Laser Imager

Room Code LASI-I
Net Room Area Briefed 2
Hours of Operation 24 Hours
Occupancy N/A
Description / Special Requirements An open bay to accommodate a dry laser camera for printing of digital images, located within the Medical Imaging Unit. The Laser Camera area should have ready access to Imaging Procedures Rooms.
Amendment 24.10.2010 First Draft 14.06.2019 Room name, area and room code updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3000 Wall finish Paint Acrylic, washable
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required; other heights also acceptable as per project standardisation
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
2767 Cornice Plasterboard Paint Square set

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
9636 Digitiser: X-ray film 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
9143 Laser imager, benchtop 3 1 yes yes ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 to laser imager/ digitiser
5000 Airconditioning HVAC
2189 General LED Lighting
2578 PO: Emergency power, double Power 2 to laser imager/ digitiser