Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
LNPA-12-I
Net Room Area Briefed
12
Hours of Operation
24 Hours
Occupancy
Up to 6 visitors
Description / Special Requirements
The Parent Lounge provides a change of environment away from clinical areas for parents or visitors to patients in the Paediatric/ Adolescent Unit. An external outlook is desirable.
Acoustics: Sound attenuation level - Medium; Acoustic privacy required.
Amendment
24.10.10, - First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5060
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x1200
7001
Windows
desirable
949496
Skirting
Timber
Paint
150mmH x 20mm thick, nominal
or floor vinyl coved skirting
6025
Cornice
Aluminium
Powdercoat
shadow line
7030
Observation
Alum/ Glass
Powdercoat
Internal window, door height
optional
9002
Doors
Solid Core/ Glass
Paint
Single leaf, half glazed
920 mm clear opening, small leaf optional
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
1149
Floor finish
Carpet
90/10 Wool/ Nylon
Broadloom, 48 oz.
Vinyl also acceptable
3000
Wall finish
Paint
Acrylic, washable
8040
Door protection
Composite
Prefinished PVC
To door frame
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
350
Artwork
Furniture/ Fitting
3
2
optional
1250
Blind: Venetian
Metalwork
3
1
to internal windows, optional
2000
Chair: lounge
Furniture/ Fitting
3
5
4900
Curtain track: window
Metalwork
1
1
5410
Curtain: window, drapes
Furniture/ Fitting
3
1
or blinds
22800
Table: low
Furniture/ Fitting
3
3
23410
Bracket: television, wall mount
Metalwork
3
1
optional
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
on wall bracket, optional
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
on table, optional
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
1 outlet for telephone
1090
TV: MATV
Communications
1
optional
5000
Airconditioning
HVAC
6000
General fluorescent
Lighting
6046
Indirect lighting
Lighting
optional
9000
GPO: Single
Power
4
9060
GPO: Special: for equipment
Power
1
TV, optional