1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code MRICR-I
Net Room Area Briefed 12
Hours of Operation Available 24 Hours
Occupancy Up to 3 staff
Description / Special Requirements Room adjacent to CT Scanning Room/s with direct visibility to the patient's full body for remote control of equipment, and review and reporting of procedure images. The Control room may serve two procedure rooms. Acoustics: Acoustic privacy is required Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Cable ducts from CT Scanning and Computer room may be required
Amendment 25.06.2019 First Draft 03.09.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
1219 Door Protection Composite Prefinished PVC Kickplate, 300mm high
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm or set plasterboard ceiling if scanning room is provided within an operating environment
9001 Doors Solid Core Paint Single leaf staff entry/ exit; 920mm clear opening
6345 Observation RF glass Clear Internal window

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
2100 Chair: ergonomic, office Furniture/ Fitting 3 2
5598 Shelving unit: adjustable, full height Furniture/ Fittings 1 1 manuals, educational material
9100 Hook: heavy duty Metalwork 1 2 for lead aprons
1050 Bench: laminate Furniture/ Fitting 1 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___
9092 Control console 2 yes yes ___ ___ ___ ___ ___ ___ part of MRI scanning unit
35860 Monitor: CCTV 3 yes yes ___ ___ ___ ___ ___ ___ part of MRI scanning unit

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3 to control console and computers
1040 Intercom Communications 1 with handsfree microphone to MRI scanning room
5000 Airconditioning HVAC
2189 General LED Lighting
2411 Special: "MRI In Use" light Lighting 1
2578 PO: Emergency power, double Power 1 to wall
2726 PO: UPS, double Power 6 to control console and computers
6005 Dimmable Lighting