Room for MRI scanning procedures, with adjacent control room and computer room. A staff handwashin basin will be located outside the room in close proximity. Fixtures and fittings to be non magnetic.
Body Protected electrical area
Acoutsics: acoustic privacy required for ambient noise emitted by scanning equipment
Special Design Requirements:
- The MRI suite shall be planned to conform to staged access and
control zones complying with local authority requirements to prevent
unscreened persons accessing the 5-gauass volume around the
MRI scanner and to minimise radiofrequency interference from other
equipment
- Electromagnetic sheilding (radio frequency enclosure) as advised by
RF Shielding Consultant
- Structural assessment may be required to ensure the floor is designed
to acommodate the weight of the equipment
- Floor to ceiling cable duct with removable covers may be required
- Underfloor cable trays between Control area and MRI table and floor to
ceiling duct may be required
- Warning lights outside each entry door
- Power to be on emergency supply - all power to MRI to pass through
MRI isolation transformer
- Installation of the MRI including services requirements such as
cryogen venting, emergency exhaust, passive pressure relief systems,
shall conform to local authority requirements and manufacturer's
specifications
Amendment
01.02.2011 First Draft
15.03.2017 Description & services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
at 3000mm height
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
6025
Cornice
Aluminium
Powdercoat
shadow line
9110
Doors
Solid Core
Paint
1 1/2 leaf
patient entry/ exit; 1400mm clear opening
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
6345
Observation
RF glass
Clear
Internal window
to control room
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
1
to patient services panel; non-magnetic
1465
Bracket: suction bottle
Furniture/ Fitting
2
1
non-magnetic
3350
Clock: battery operated
Furniture/ Fitting
3
1
non-magnetic
16250
Oxygen flowmeter
Furniture/ Fitting
3
2
to patient services panel; non-magnetic
21950
Suction adapter
Furniture/ Fitting
3
2
to patient services panel; non-magnetic
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
7300
Camera: CCTV security
1
3
yes
___
___
___
___
___
___
___
to view patient, optional
66750
IMG: MRI imaging unit
3
1
yes
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
1 outlet for telephone
1040
Intercom
Communications
1
handsfree to Control Room
5000
Airconditioning
HVAC
6001
General: colour corrected
Lighting
6110
Downlights: dimmable
Lighting
7000
Oxygen (O2)
Medical Gases
2
patient services panel; non magnetic outlet
7010
Nitrous Oxide (N2O)
Medical Gases
1
patient services panel; non magnetic outlet
7020
Medical Air (MA)
Medical Gases
1
patient services panel; non magnetic outlet
7040
Suction
Medical Gases
2
patient services panel; non magnetic outlet
7070
Scavenge
Medical Gases
1
patient services panel; non magnetic outlet
8010
Staff/ Nurse assist call
Nurse Call
1
8080
Emergency call
Nurse Call
1
2579
PO: Emergency power, single
Power
4
patient services panel
9011
GPO: Emergency power, double
Power
3
walls
9040
Body protected
Power
2587
PO: Special: for equipment
Power
1
MRI Imaging equipment, Control and computer equipment modules; refer to Manufacturer's specifications